Installation 

Mounting on electric box 

 
1.  Separate back plate from the controller by loosing the cover screw; 
2.  Align the mounting holes on the screw holes of the electric box(applicable to 65x65 or US standard box); 
3.  Fix the back plate on the electric box by tightening the back plate screws. Suggest to use Philips wider “truss head” or 

“washer head” #6-32x 3/4”(20mm).  

4.  DO NOT let the bolt head rise above the wall of mounting holes of back plate. It might cause the short circuit of the 

controller. 

Mounting front cover 

 
1.  Lock front cover on the back plate by tightening the cover screw underneath with Philip screw driver.  

Wiring Example 

 

1.

 

All wires  must be inserted above the retainers of respective terminal block before tightening the captive 
screws; 

WIRING DIAGRAM FOR TE226 – 24Vac Thermostat 

 

 

   2.   Select Normally Open or Normally Closed Cooling and Heating valve Option in the Engineering Mode          

parameter E20 and E21 

 

ON DEMAND OUTPUT DO1 AND DO2 

   

 

Set in Engineering Mode 

   

 

 

 

   

 

DO1 Cooling Output   

on demand for 

cooling 

Parameter E20 

Set To : 

 

DO2 Heating Output  

on demand for 

heating 

Parameter E21 

Set To: 

0 Vac 

 

0 Vac 

24 Vac 

 

24 Vac 

 

AO2 

RS 

ESI 

ECM   Fan-0~10VDC 

Remote Temperature 
Sensor(NTC10K) 

Occupancy 

Summary of Contents for TE226 Series

Page 1: ...et point temperature while it is flashing 8 Fan icons Indicate Fan status 9 Flake icon Indicate working in Cooling mode 10 Hot spring icon Indicate working in Heating mode 11 Flow icon Indicate workin...

Page 2: ...ntroller Mounting front cover 1 Lock front cover on the back plate by tightening the cover screw underneath with Philip screw driver Wiring Example 1 All wires must be inserted above the retainers of...

Page 3: ...splay Display Current Room or Set Point Temperature and Current Time Day Setting SP Parameter in Engineer Table to Choose Current Room or Set Point Temperature 2 Temperature Setting Set The Required T...

Page 4: ...Revised Date 2018 04 24 4 Fig 2 User Mode operation sequence...

Page 5: ...Revised Date 2018 04 24 5 Overview for the settings of Clock and Programmable Schedules Press MODE FAN or POWER button to escape any time during setting...

Page 6: ...Revised Date 2018 04 24 6 1 Detailed State Diagram for Clock Setting...

Page 7: ...for Schedule Setting Press Mode button to select day shows steadily deselect day flash Press MODE button to toggle Cooling Heating Set points Press MODE button to toggle Cooling Heating Set points Pre...

Page 8: ...8 00 16 0 8 00 16 0 Sch 3 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 Sch 4 22 00 16 0 22 00 16 0 22 00 16 0 22 00 16 0 22 00 16 0 22 00 16 0 22 00 16 0 l Unoccupied S...

Page 9: ...the LCD Stage On Current Temperature Cooling Stage Differential Dead Band Heating Stage Differential SP Cooling and Heating Control Auto Changeover Dead band Option 0 OFF Stage On Current Temperature...

Page 10: ...or delivery outside air from suite HRV or OA vent duct If there is a call for heating or cooling the fan would ramp up to maximum design airflow for the FCU on the project 3 Fan Mode By pressing FAN b...

Page 11: ...on the LCD c STOP mode means using manual S P instead of all Schedules i e Temporarily disable all programmable Schedules And the icon will be NOT shown on the LCD Examples of Engineering Mode 5 E19...

Page 12: ...ress UP or DOWN button to change the setting and press MODE button to confirm the setting and return to menu item selection For no button pressed for 10 seconds it will go back to menu item selection...

Page 13: ...Adjustment for FAN control 25 150 0 25 150 0 1 0 044V E9 SP L Low Limit for Temperature Set Point 10 0 0 50 0 50 0 32 0 122 0 1 0 C F E10 SP H High Limit for Temperature Set Point 35 0 0 50 0 95 0 32...

Page 14: ...lay SP E17 FAnL Lowest Fan Speed in Continuous Fan Mode 25 0 100 25 0 100 1 E18 Fan2 Medium Fan Speed 60 20 100 60 20 100 1 E19 dLAy Minimum delay time between cooling and heating 0 0 5 0 0 5 1 minute...

Reviews: