background image

Revised Date: 2018/04/24 

12 

 
Engineer Mode Operation 

 

This mode is highly suggested to be operated by trained engineers because it is related to system parameters that 
will affect the control results. To operate: 
 
1. Press “Up” and “Down” buttons for over 5 seconds to enter into engineer mode; 
2. Press UP or DOWN button to rotate the menu item and press MODE button to enter into the item; 
3. Press UP or DOWN button to change the setting and press MODE button to confirm the setting and return to 
menu item selection. For no button pressed for 10 seconds, it will go back to menu item selection. The setting won’t 
be changed then. 
4. To leave Engineer Mode, rotate till “End” and press MODE button or leave the button intact for 10 seconds.  
Engineer mode operation flow chart: 

 
 
 
 
 

 

 

 

 

Fig. 3  Engineer Mode operation sequence 

 
 

 

E01 

 

E02 

 

 

End 

MODE 

 

E01 Setting 

MODE 

User Mode 

MODE 

 

E02 Setting 

MODE 

MODE 

Previous 

No button pressed for 
10s under menu item 
selection 

Press Up/down 
for over 5s

 

Summary of Contents for TE226 Series

Page 1: ...et point temperature while it is flashing 8 Fan icons Indicate Fan status 9 Flake icon Indicate working in Cooling mode 10 Hot spring icon Indicate working in Heating mode 11 Flow icon Indicate workin...

Page 2: ...ntroller Mounting front cover 1 Lock front cover on the back plate by tightening the cover screw underneath with Philip screw driver Wiring Example 1 All wires must be inserted above the retainers of...

Page 3: ...splay Display Current Room or Set Point Temperature and Current Time Day Setting SP Parameter in Engineer Table to Choose Current Room or Set Point Temperature 2 Temperature Setting Set The Required T...

Page 4: ...Revised Date 2018 04 24 4 Fig 2 User Mode operation sequence...

Page 5: ...Revised Date 2018 04 24 5 Overview for the settings of Clock and Programmable Schedules Press MODE FAN or POWER button to escape any time during setting...

Page 6: ...Revised Date 2018 04 24 6 1 Detailed State Diagram for Clock Setting...

Page 7: ...for Schedule Setting Press Mode button to select day shows steadily deselect day flash Press MODE button to toggle Cooling Heating Set points Press MODE button to toggle Cooling Heating Set points Pre...

Page 8: ...8 00 16 0 8 00 16 0 Sch 3 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 Sch 4 22 00 16 0 22 00 16 0 22 00 16 0 22 00 16 0 22 00 16 0 22 00 16 0 22 00 16 0 l Unoccupied S...

Page 9: ...the LCD Stage On Current Temperature Cooling Stage Differential Dead Band Heating Stage Differential SP Cooling and Heating Control Auto Changeover Dead band Option 0 OFF Stage On Current Temperature...

Page 10: ...or delivery outside air from suite HRV or OA vent duct If there is a call for heating or cooling the fan would ramp up to maximum design airflow for the FCU on the project 3 Fan Mode By pressing FAN b...

Page 11: ...on the LCD c STOP mode means using manual S P instead of all Schedules i e Temporarily disable all programmable Schedules And the icon will be NOT shown on the LCD Examples of Engineering Mode 5 E19...

Page 12: ...ress UP or DOWN button to change the setting and press MODE button to confirm the setting and return to menu item selection For no button pressed for 10 seconds it will go back to menu item selection...

Page 13: ...Adjustment for FAN control 25 150 0 25 150 0 1 0 044V E9 SP L Low Limit for Temperature Set Point 10 0 0 50 0 50 0 32 0 122 0 1 0 C F E10 SP H High Limit for Temperature Set Point 35 0 0 50 0 95 0 32...

Page 14: ...lay SP E17 FAnL Lowest Fan Speed in Continuous Fan Mode 25 0 100 25 0 100 1 E18 Fan2 Medium Fan Speed 60 20 100 60 20 100 1 E19 dLAy Minimum delay time between cooling and heating 0 0 5 0 0 5 1 minute...

Reviews: