Ensure that all hoses, pipe fittings, and connectors are fully tightened and leak tested.
CAUTION
ALL PIPE JOINTS AND CONNECTIONS MUST BE TESTED THOROUGHLY FOR GAS LEAKS.
USE ONLY SOAPY WATER FOR TESTING ON ALL GASES. NEVER USE AN OPEN FLAME TO
CHECK FOR GAS LEAKS. ALL CONNECTIONS MUST BE CHECKED FOR LEAKS AFTER THE
UNIT HAS BEEN PUT INTO OPERATION. TEST PRESSURE SHOULD NOT EXCEED 14" (356mm)
W.C.
The gas pressure regulator supplied with the unit is set to deliver to the manifold a 6" (152mm) W.C.
pressure for natural gas and a 10" (254mm) W.C. pressure for propane. Before making any adjustments
that are affected by the manifold gas pressure, first test the gas pressure using the “Adjusting Gas
Pressure Regulator” procedure on page 23 of this manual. The test should be performed with all other gas
equipment operating.
Step 6: Check the Installation
Check the installation, as follows:
1. Check that all screws and bolts are tightened.
2. Check electrical connection, including proper grounding.
3. Check that the gas connection has been made correctly.
4. Move the unit into the final position at which it will be operated.
5. For units with casters, check that the restraint has been properly installed and is connected.
6. Check that the unit is level. If not, adjust the legs or casters.
Quick Disconnect
External Piping
Connection
(1" NPT)
Swivel
Swivel
Flex Hose