Confidential
MANUAL
44(51)
Document number
Revision
7/198 17-LXE 108 566 Uen
A
Note: Any hard copy of this document is for reference only.
Due to template and application dependencies the header and footer may fail to display correct data. It is the
responsibility of the user to ensure that they have a correct and valid version. Any outdated hard copy is invalid and must be removed from possible use.
Figure 30: Phone Module, Power ON/OFF
Note:
For more information and precautions on module shutdown, see section 6.4 below.
4.2 Alarm
Application
Wakeup
The application can setup an alarm inside GM41 which will wakeup the phone-module at a specific time. This
feature makes use of the following signals:
•
VREF
•
VRTC
It furthermore requires the serial channel TD and RD to setup the real time clock (AT+CCLK) and the alarm time
(AT+CALA).
VREF:
The phone module reference voltage goes active high (0.8V to 2.0V) for 250ms when the alarm activates. The low-
to-high transition of this signal shall be used to wake up the application. The application then performs a normal
power up sequence.
VRTC:
The implementation of the real-time clock voltage (VRTC) can differ depending on the application:
•
In a cheap solution the application could apply 1.8V on VRTC using a regulator.
•
If low current consumption is required, the application could use a super-cap which would be charged by
the phone-module while it is operating, relying on the cap providing power when it is powered down.
•
If the application would wake up for short periods and stays powered down for long periods; the use of a
regulator might be required since the cap might not be able to sustain power.
Sequence:
1.
Alarm is activated. The phone-module output a high pulse (250ms) on VREF.
2.
The application has detected the positive pulse on VREF and enables both 5V power supplies and sets
MODULE_PWR_EN_B active low.