GB
24
Installation & Operating Manual 12/2013
2.6
Avoiding damage to property
on-site thermal solar system and heating system
X
Before installation of the station, flush on-site thermal solar system and heating system sufficient-
ly in accordance with VDI 2035 and DIN-EN 14336.
Safety equipment in the solar circuit
For a connection line >200 kW, the system requires an additional safety valve in the solar circuit.
X
Provide a blow-off line in accordance with DIN 1988 for the solar circuit.
X
Provide a shut-off valve with sealing possibility or cap shut-off valve of a suitable size on-site for
connection to a diaphragm expansion tank (MAG).
Safety equipment in backup circuit
The system has a safety valve for self protection in the backup circuit.
X
Provide an additional safety valve suitable for the size of the system on site in the backup circuit.
X
Provide a blow-off line in accordance with DIN 1988 for the backup circuit.
Repairs
X
Have repairs made only by specialist personnel.
X
Use only original spare parts.
Materials and components used on site must be unrestrictedly suitable for the intended purpose of
use and must have been tested or approved by the manufacturer. They must also satisfy applicable
laws, standards, directives and regulations.
X
Use only such materials and components.
X
Do not make unauthorized changes to the stratified charging module.
X
If there is damage to the system: Do not continue to operate the system.
3
tools and supplies
X
Do not use pipe wrenches for installing valves and fittings with spanner flats.
X
Use ordinary tools and consumables.
4
Supply scope
Material
Quanti-
ty
note
Stratified charging module
SLM120/200/300HE
1
Including primary and secondary safety
valves
Panel screws
4
Fasteners for wall installation
Screw anchors for masonry
4
Fasteners for wall installation
Styring
1
Pre-assembled plug-in ready
Shut-off ball valves
5
4 included
Cover including insulation
1
Optionally available
Installation and operating manual
1
Included
Styring operating manual
1
Included
Technical documentation for pumps
3
Included
Technical documentation for three-way
changeover valve
1
Included