GB
36
Installation & Operating Manual 12/2013
X
Return system to seller or manufacturer.
17 technical data
17.1
Design and operating data
17.1.1
Stratified charging Module
SLM120HE
SLM200HE
SLM300HE
Dimensions [L x W x H mm]
1086 x 691 x 291
1119 x 746 x 356
1119 x 746 x 356
Weight [kg]
90
115
120
Connections
6/4"
2"
2"
Spread, prim./sec. [°C]
60/35 - 54/29
Flow, prim./sec. [m^3/h]
2.37 / 2.05
4.6 / 4.2
6.9 / 6.2
Pressure loss, prim./sec. [kPa]
2.3 / 1.6
5.83 / 7.07
7.36 / 8.62
WT transmission power [kW]
60
120
180
Pumps (Wilo Stratos Para)
prim.
sec.
25/1-12
Z 25/1-8
30/1-12
Z 30/1-8
30/1-12
Z 30/1-8
Rated voltage [V/Hz]
230 / 50
Degree of protection
IP 40
Power consumption,
prim./sec. [W]
16 - 31 / 08 - 130
Max. current draw,
prim./sec. [A]
0.16 - 1.37 / 0.07 - 0.95
Max. delivery head,
prim./sec. [m]
12 / 8
Perm. operating temperature
prim./sec. [°C]
110 / 90
Perm. operating pressure,
prim./sec. [bar]
10 / 10
Solar/backup piping
Stainless steel
Plate heat exchanger
Stainless steel
Plates and supports
Stainless steel 1.4400
Solder
99.99% copper
Seals
AFM
Flow measurement range [l/min]
10 - 200
17.1.2 Styring
Technical data in accordance with third party manual for styring.