Electrical Installation
6
6.10.2 Connecting the PV system
DC voltage too high
Danger to life due to electrocution!
►
Only connect PV systems whose unloaded voltage does not exceed the
maximum voltage for the PV inputs.
Plugging in/unplugging PV lines during operation
Serious burns trough arcing!
Before plugging in/unplugging PV lines:
►
Switch the PV disconnector (SPV) off.
Prerequisite:
✔
The maximum input current of the PV inputs (see 3.1 – 11) must not be
exceeded.
✔
The unloaded voltage of the PV system must never exceed the maximum input
voltage (see 3.1 – 11) for the PV inputs. Please note that the unloaded voltage of
PV systems depends upon the ambient conditions (particularly the temperature).
►
Remove the protective caps from
the PV connections XPVP and XPVM.
►
Keep the caps in a safe place.
►
Connect the PV plus wire (2) to the
XPVP connection
►
Connect the PV minus wire (3) to
the XPVM connection.
1
PV system
2
PV plus line
3
PV minus line
XPVP
PV plus connection
XPVM PV minus connection
Figure 49: Connecting the PV system to
the storage system
KD-421 | Part no. 22136 | EN | X03
55 / 68