6
Electrical Installation
6.8.4 Setting the termination switches
Figure 39: Setting the termination switch
on the battery module with the highest
number
►
Slide the termination switch (switch
4) of the battery module with the
highest number up (switch position
ON).
For example, in the case of a storage
system with a total of three battery
modules (No. 0, 1 and 2), the
termination switch on battery module 2
must be set to ON.
►
Ensure that the termination
switches of all other battery modules
are in switch position OFF.
6.8.5 Positioning the battery modules
1
0
1
2
3
4
5
6
7
►
Position the battery modules as shown in figure
40.
The first battery module (Number 0) is positioned
right at the bottom in the extension cabinet. The
numbering of the battery increases from the bottom
to the top.
Figure 40: Positioning the
battery modules
46 / 68
KD-421 | Part no. 22136 | EN | X03