Via KNXnet/IP Routing 

Programming via KNXnet/IP Routing is possible if the device 

already has a valid IP configuration (e.g. by using DHCP or Auto 

IP). In the ETS, the routing interface appears if at least one 

device on the network which supports routing is available. The 

name of the network interface appears in the PC as description. 

If routing is selected as interface, the programming is done from 

the ETS project as like with other devices. In this case LAN is 

used as a KNX medium like TP. There is no additional interface 

device required. 

Via direct IP connection 

While KNXnet/IP Tunneling and KNXnet/IP Routing is limited to 

the speed of KNX TP the device can be loaded via a direct IP 

connection at high speed. The direct IP connection is possible if 

the device already has a valid IP configuration as well as an 

individual address. To do this select "Use direct IP connection if 

available" in the ETS menu "Bus – Connections - Options". The 

download is then directly performed in the device and is not 

visible in the ETS group monitor. 

  

Due to the significantly shorter transmission times it is 

recommended to perform downloads via IP. 

 

 

       WARNING 

 

  The device must be mounted and commis-

sioned by an authorized electrician. 

  The prevailing safety rules must be heeded. 

  The device must not be opened. 

  For planning and construction of electric in-

stallations, the relevant guidelines, regulations 

and standards of the respective country are to 

be considered. 

 

 

 

 

SOMFY ACTIVITÉS SA 

50 Avenue du Nouveau Monde  

74300 Cluses  

France 

T +33 (0)4 50 96 70 00  

F + 33 (0)4 50 96 71 89  

www.somfy.com/projects  

 

Société Anonyme 

Capital: 35.000.000 € 

RCS ANNECY 303.970.230 

Summary of Contents for KNX IP LineMaster

Page 1: ...aster operates as a line or backbone coupler In both cases the LAN IP is used as a backbone The following table shows the application possibilities of the KNX IP LineMaster compared to the classic top...

Page 2: ...flashes quickly The programming mode is not active The rapid flashing indicates one of the following faults o Overload sum of the current of auxiliary and Bus power o The device is not loaded correct...

Page 3: ...nged on the subline TP ROUT Acknowledge only when forwarding ACK acknowledge al ways NACK negative acknowledgment When answering with NACK access to the device via KNX TP is no longer pos sible see ET...

Page 4: ...d via an ETS project See the ETS database section for more information As factory default the assignment of the IP address is set to automatically via DHCP no further IP settings are necessary To use...

Page 5: ...changes in the properties menu become effective on ly after a successful application download IP address Here the IP address of the KNX IP LineMaster can be entered This is used to address the device...

Page 6: ...e routed to IP Route All group telegrams of this main group are routed to IP independent of the filter table This setting is used for testing purposes on ly Filter The filter table is used to check wh...

Page 7: ...ived group telegram should be routed to KNX TP Individually addressed telegrams Block No individually addressed telegrams are routed to KNX TP Route All individually addressed telegrams are routed to...

Page 8: ...be loaded via a direct IP connection at high speed The direct IP connection is possible if the device already has a valid IP configuration as well as an individual address To do this select Use direc...

Reviews: