background image

 

©

2017 SOMFY ACTIVITÉS SA, 50 avenue du Nouveau Monde, 74300 Cluses, France REF. 5135987B – 2017-06-30 

Page 2/8

 

 

KNX IP LineMaster as area and line coupler 

 

The KNX IP LineMaster has a filter table and thus contributes to 

reducing the bus load. The filter table (8kB) supports the extend-

ed group address range and is automatically generated by the 

ETS. 

Because of the speed difference between the Ethernet (100 

Mbit/s) and KNX TP (9.6 kbit/s), a far greater number of tele-

grams can be transmitted on IP. If several consecutive telegrams 

are transmitted for the same line, they must be buffered in the 

router to avoid telegram loss. The KNX IP LineMaster has a 

memory for 150 telegrams (from IP to KNX). 

 

Bus access function (KNXnet/IP Tunneling) 

The KNX IP LineMaster can be used as an interface to KNX. The 

KNX bus can be accessed from any point in the LAN. The device 

supports up to 6 simultaneous Tunneling connections. For each 

connection an additional individual address must be assigned. 

This is described in the following sections. 

 
Installation and Connection 

The KNX IP LineMaster is designed for installation on DIN rail 
with a width of 6 units (108 mm). It features the following controls 
(

❼❽❾

) and displays (

): 

 

 

Settings 

The settings  of the device can be accessed via  

1.  Local display on the device (partly) 

2.  ETS (Version 4.2 or higher)

 

 

 

The KNX Programming Mode is activated/deactivated by 

simultaneously pressing the buttons 

❽❿

 

– when acti-

vated the programming LED 

 

lights up. 

 

Programming and status LED 

 

The red LED on the front panel is used to display the KNX pro-

gramming mode and errors. The LED can have the following 

states: 

 

LED off: The programming mode is not active and 

there is no error (normal operating mode). 

 

LED lights up: The programming mode is active, 

any errors are not visualized/notified by the LED, 

but can be read on the display. 

 

LED flashes quickly: The programming mode is 

not active. The rapid flashing indicates one of the 

following faults: 

o

 

Overload (sum of the current of auxiliary 

and Bus power) 

o

 

The device is not loaded correctly, for 

example, a cancelled download. 

Factory default settings 

The following configuration is set by factory default: 

Individual device address: 

 

 

15.15.0 

Number of configured KNXnet/IP tunneling con.:  6 

Individual address of tunneling con. 1:   

15.15.240 

Individual address of tunneling con. 2:   

15.15.241 

Individual address of tunneling con. 3:   

15.15.242 

Individual address of tunneling con. 4:   

15.15.243 

Individual address of tunneling con. 5:   

15.15.244 

Individual address of tunneling con. 6:   

15.15.245 

IP address assignment: 

 

 

DHCP 

 

Direct Setting via display on device 

A.  Startup and idle display 

During startup of the device, the physical 

address and the status of the application 

is displayed. 

The device name “KNX IP LineMaster” 

can be changed within ETS parameter 

settings. 

 

The status can be one of the following values: 

 

Running:

 Application is loaded and running 

 

Stopped:

 The application is stopped -

 

LED for 

Programming Mode is flashing 

 

Unloaded: 

The application is not loaded- 

 

LED 

for Programming Mode is flashing 

 

Loading:

 The application is currently loading by 

ETS 

 

Overload:

 The output current is above the limit of 

900mA - 

 

LED for Programming Mode is flash-

ing 

 

Manual:

 Parameterized coupler settings were 

manually overwritten (filter, repetition and 

acknowledge) via the manual operation in the de-

vice display. By pressing long on on Enter 

, the 

normal operating mode, as parameterized, is re-

stored. 

The power supply functionality (KNX and auxiliary voltage) is 

not dependent whether the application is running or not. 

After 10 minutes of inactivity the display will turn into 

screensaver mode (blank screen with a bouncing dot) to 

safe display life time. Press any key to turn the display 

on again. 

 

 

 

Aux. Power Out 30 V DC 

 

KNX Bus Out 

 

Power In 230 V AC 

 LAN Connector 

 OLED Display 

 LED for Prog. Mode 

 Up Button 

 Down Button 

 Escape Button 

 Enter Button 

 

 

Summary of Contents for KNX IP LineMaster

Page 1: ...aster operates as a line or backbone coupler In both cases the LAN IP is used as a backbone The following table shows the application possibilities of the KNX IP LineMaster compared to the classic top...

Page 2: ...flashes quickly The programming mode is not active The rapid flashing indicates one of the following faults o Overload sum of the current of auxiliary and Bus power o The device is not loaded correct...

Page 3: ...nged on the subline TP ROUT Acknowledge only when forwarding ACK acknowledge al ways NACK negative acknowledgment When answering with NACK access to the device via KNX TP is no longer pos sible see ET...

Page 4: ...d via an ETS project See the ETS database section for more information As factory default the assignment of the IP address is set to automatically via DHCP no further IP settings are necessary To use...

Page 5: ...changes in the properties menu become effective on ly after a successful application download IP address Here the IP address of the KNX IP LineMaster can be entered This is used to address the device...

Page 6: ...e routed to IP Route All group telegrams of this main group are routed to IP independent of the filter table This setting is used for testing purposes on ly Filter The filter table is used to check wh...

Page 7: ...ived group telegram should be routed to KNX TP Individually addressed telegrams Block No individually addressed telegrams are routed to KNX TP Route All individually addressed telegrams are routed to...

Page 8: ...be loaded via a direct IP connection at high speed The direct IP connection is possible if the device already has a valid IP configuration as well as an individual address To do this select Use direc...

Reviews: