animeo KNX 4 AC Motor Controller
30.01.2019
WM/DRM 220-230 V AC
2011-2019, SOMFY Activites SA
50 avenue du Nouveau Monde
74300 Cluses
France
26/55
When the local push button inputs are used as universal push button inputs, the operating ergonomics are
defined over the corresponding parameters (short/long pressing of the push button). The operating ergonom-
ics using a Somfy RTS radio transmitter remains unchanged.
H
For an explanation of EU/US ergonomics and screen ergonomics see chapter 1 Definitions.
•
Window
With this parameter it is determined that the corresponding window is selected over move/stop commands
when the controlling is done over the local push button inputs or via the Somfy RTS radio hand transmitter.
When the local push button inputs are used as universal push button inputs, the operating ergonomics are
defined over the corresponding parameters (short/long pressing of the push button). The operating ergonom-
ics using a Somfy RTS radio transmitter remains unchanged.
H
For an explanation of EU/US ergonomics and screen ergonomics see chapter 1 Definitions.
6.2.2 Running time Up/Close
Default value:
120 seconds
Selection options:
0.1 - 320 seconds
The time parameterized here is the maximum running time from the lower end position to the upper end posi-
tion, or the maximum running time which a window motor needs to close the corresponding window. An ex-
cess time of 5 seconds is always added, except with position telegrams (objects 13-16). If a position tele-
gram with the value
“0” is sent to the corresponding object, an excess time of 5 seconds is still added to it.
6.2.3 Running time Down/Open
Default value:
120 seconds
Selection options:
0.1 - 320 seconds
The time parameterized here is the maximum running time from the lower end position to the upper end posi-
tion or the maximum running time which a window motor needs to open the corresponding window. An ex-
cess time of 5 seconds is always added to it, except with position telegrams (objects 13-16). If a position tel-
egram with the value
“100” is received on the corresponding object, an excess time of 5 seconds is still
added to it.
6.2.4 Tilting time from 90° to 0°
Default value:
1.3 seconds
Selection options:
0 - 20 seconds
The parameterized time here is the maximum tilting time of the slats. This parameter is only visible when the
“Type of end product” is set to Venetian blind with EU ergonomics or Venetian blind with US ergonomics.
H
For an explanation of EU/US ergonomics see chapter 1 Definitions.
6.2.5 Step length
Default value:
0.2 seconds
Selection options:
0.1 - 10 seconds
The parameterized time here is the move time for a turn step. This parameter is only visible when the type of
end product, Venetian blind with EU ergonomics or Venetian blind with US ergonomics is selected.
H
For an explanation of EU/US ergonomics see chapter 1 Definitions.