6.2.8.1 Cyclic monitoring time in minutes (0
–255)
Default value:
0
Selection options:
0 - 255 minutes
The cyclic monitoring time is active and refers to the high and low priority security objects.
H
The cyclic transmitter must be approximately 4 times faster than the cyclic monitoring. E.g. if the cyclic
sending of the transmitter is set to 1 minute, then the cyclic monitoring time should be set to
≥4 minutes.
6.3 Menu index card
“Functions for motor 1...4”
Four single menu index cards (Functions motor
1…4) become visible if on the menu card index “General”,
the basic setting of the blinds on
“Individual” is parameterized. A menu index card (Motor 1 - 4) becomes visi-
ble if on the menu card index
“General”, the basic setting of the motors is parameterized to “Combined”.
6.3.1 Intermediate Position 1 (IP1)
6.3.1.1 Up/Down position (0-100%)
Default value:
0 % (function disabled)
Selection options:
0 - 100 %
With this parameter the intermediate position 1
“UP/DOWN” is defined. The set value in % refers to the pa-
rameterized move times of the corresponding blind of the menu index card Motor
1…4/Motor 1 - 4.
If the IP UP/Down position parameter is set to 0 %, the IP position is disabled. This function avoids any
movement of the blinds by using the “my” or IP push button.