animeo KNX 4 AC Motor Controller
30.01.2019
WM/DRM 220-230 V AC
2011-2019, SOMFY Activites SA
50 avenue du Nouveau Monde
74300 Cluses
France
27/55
6.2.6 Slack compensation
Default value:
0 seconds
Selection options:
0 - 5 seconds
The time slack compensation is active as soon as a higher value than
“0” is entered. The time parameterized
here defines the time which is added to the parameterized complete slats turn to balance out mechanical tol-
erances. This time is always added with the first UP turn of the slats when the type of end product, Venetian
blinds with EU ergonomics or Venetian blinds with US ergonomics have been selected.
H
For an explanation of EU/US ergonomics see chapter 1 Definitions.
6.2.7 Security position Low priority
Default value:
Ignore security
Selection options:
Upper end limit
Lower end limit
Intermediate position 1 (IP 1)
Intermediate position 2 (IP 2)
Ignore security
Stop
Close window
Open window
The
“Security position low priority” for the corresponding blind is determined with this parameter. If a tele-
gram with the value
“1” is received on one of these communication objects (objects 40-43) the corresponding
blind moves to the position parameterized in the ETS parameters.
If a telegram with the value
“0” is received on one of these communication objects, no operation is carried
out. If the function
“Repeat last telegram after security” is set with “Yes” in the menu index card “Functions
motor 1...4”, the blind moves, after ending of the “Low priority” (value “0”), again in the last position and angle
before activation of this priority.
6.2.8 Security position High priority
Default value:
Upper end limit
Selection options:
Upper end limit
Lower end limit
Ignore security
Stop
Close window
Open window
The
“Security position high priority” for the corresponding blind is determined with this parameter. If a tele-
gram with the value
“1” is received on one of these communication objects (objects 45-48), the correspond-
ing blind moves to the position parameterized in the ETS parameters.
If a telegram with the value
“0” is received on one of these communication objects, no operation is carried
out.
If the function
“Repeat last telegram after security” is set with “Yes” in the menu index card “Functions motor
1…4”, it is checked whether “Low priority” is active or inactive. When “Low priority” (value “1”) is active the
blinds move to the parameterized
“Security position low priority” (see previous point). If the “Low priority”
(value
“0”) is also inactive, the blind moves again to the last position with the last angle before activating the
high and low priorities.