5 Communication objects
5.1 Object overview
At the most, 177 communication objects are available for use, but not all at once. A maximum of 250 group
addresses can be connected.
5.1.1 List of Objects
No. Object name
Type
DPT_ID Description
1
Motor 1 Up/Down, Close/Open
1 bit
1.008
If a telegram with the value “0” is received on this
communication object, the appropriate blind goes
up or the window closes. If a telegram with the
value “1” is received, the appropriate blind goes
down or the window opens. At expiration of the
adjusted running time for the UP and DOWN di-
rection the relays of the outputs are deactivated.
2
Motor 2 Up/Down, Close/Open
1 bit
1.008
3
Motor 3 Up/Down, Close/Open
1 bit
1.008
4
Motor 4 Up/Down, Close/Open
1 bit
1.008
9
Motor 1 Step/Stop
1 bit
1.008
With Venetian blinds: If the Venetian blind is
moving, the move is stopped with the receiving of
a telegram on one of these communication ob-
jects, no matter whether
“0” or “1” is received. If
the Venetian blind is stationary, a turn is carried
out. In addition, the slats turn CLOSED with the
receiving of a telegram with the value
“1” and UP
with the receiving of a telegram with the value
“0”. The duration of the turning step is defined in
the parameter settings.
With vertical awnings, roller shutters, awnings
and windows: When one of the end products is
moving, the move is stopped with the receiving of
a telegram on one of these communication ob-
jects, no matter whether
“0” or “1” is received. If
one of these end products is not moving and a
telegram is received on one of these communica-
tion objects, then no operation is carried out.
10
Motor 2 Step/Stop
1 bit
1.008
11
Motor 3 Step/Stop
1 bit
1.008
12
Motor 4 Step/Stop
1 bit
1.008
13
Motor 1 Position Up/Down
1 Byte 5.001
If a telegram is received on one of these commu-
nication objects, the corresponding blind will
move to the position which is defined by the re-
ceived value
“0” = upper/”100” = lower.
With Venetian blinds: When the position is
reached, the same slats angle is moved to at
which the Venetian blind was before.
14
Motor 2 Position Up/Down
1 Byte 5.001
15
Motor 3 Position Up/Down
1 Byte 5.001
16
Motor 4 Position Up/Down
1 Byte 5.001
17
Motor 1 Slat position
1 Byte 5.001
With Venetian blinds: If a telegram is received on
one of these communication objects, the corre-
sponding slats will move to the position which is
defined by the received value. If a Venetian blind
18
Motor 2 Slat position
1 Byte 5.001
19
Motor 3 Slat position
1 Byte 5.001