CONTROL BOX 3S io
2
Copyright
©
2017 SOMFY ACTIVITES SA. All rights reserved.
PARAMETERS
OPERATING CODES
PROGRAMMING CODES
ERROR AND BREAKDOWN CODES
Code
Description
Values (bold = default)
Setting
P01
Complete cycle operating mode
0: sequential
1: sequ timed close
2: semi-automatic
3: automatic
4: aut cell blocking
5: deadman's control (wire)
P02
Complete operating mode
automatic timed closing
0 to 30 (time delay value = value x 10 s)
2: 20 s
P03
Pedestrian cycle operating
mode
0: identical to complete cycle operating
mode
1: without automatic closing
2: with automatic closing
P04
Short automatic closing time
delay in pedestrian cycle
0 to 30 value x 10 s = time delay value)
2: 20 s
P05
Long automatic closing time
delay in pedestrian cycle
0 to 99 (value x 5 min. = time delay value )
0: 0 s
P07
Cell safety input
0: inactive
1: active
2: active with autotest via test output
3: active with autotest via power supply
switching
4: bus cells
P09
Programmable safety input
0: inactive
1: active
2: active with autotest via test output
3: active with autotest via power supply
switching
P10
Programmable safety input -
function
0: active closing
1: active opening
2: active c ADMAP
3: all movement disabled
P11
Programmable safety input -
action
0: stop
1: stop + partial reversal
2: stop + complete reversal
P12
Orange warning light
0: no warning
1: with 2 s warning prior to movement
P13
Area lighting output
0: inactive
1: controlled operation
2: aut controlled operation
P14
Area lighting time delay
0 to 60 value x 10 s = time delay value)
6: 60 s
P15
Auxiliary output
0: inactive
1: automatic: gate open indicator light
2: automatic: timed bistable
3: automatic: one-touch
4: controlled: bistable (ON-OFF)
5: controlled: one-touch
6: controlled: timed bistable
P16
Auxiliary output time delay
0 to 60 value x 10 s = time delay value)
6: 60 s
P17
Lock output
0: active 24V one-touch
1: active 12V one-touch
P18
Lock release (Control Box 3S
Axovia only)
0: inactive
1: active
P19
Closing speed
1: slowest speed
10: fastest speed
Default value:
- Control Box 3S Axovia: 5
- Control Box 3S Ixengo: 6
- Control Box 3S Axovia 200 io: 8
P20
Opening speed
P21
Closing slowdown zone
0: zero slowing (only on Ixengo L 24V)
1: shortest slowdown zone
5: longest slowdown zone
Default value:
- Control Box 3S Axovia: 1
- Control Box 3S Ixengo: 2
- Control Box 3S Axovia 200 io: 3
P22
Opening slowdown zone
P23
M1/M2 shi when closing
0: zero shi (only on Ixengo L 24V)
1: minimum shi
10: maximum shi
Adjusted at the end of auto-programming
P24
M1/M2 shi when opening
P25
M1 closing torque limitation
1: minimum torque
10 (Axovia) or 20 (Ixengo): maximum torque
Adjusted at the end of auto-programming
P26
M1 opening torque limitation
P27
M1 closing slowdown torque
limitation
P28
M1 opening slowdown torque
limitation
P29
M2 closing torque limitation
P30
M2 opening torque limitation
P31
M2 closing slowdown torque
limitation
P32
M2 opening slowdown torque
limitation
P37
Wired control inputs
0: complete cycle mode - pedestrian
cycle
1: opening mode - closing
P39
Additional thrust when closing
(Control Box 3S Ixengo only)
0: no thrust
1: with thrust (thrust of 2.5 sec aer detection
of end limit)
P40
Coupling speed when closing
1: slowest speed
4: fastest speed
Default value:
- Control Box 3S Axovia: 2
- Control Box 3S Ixengo: 2
- Control Box 3S Axovia 200 io: 1
P41
Coupling speed when opening
Code
Description
H0
Awaiting setting
Hc1
Awaiting s 9.6 V power supply
Hu1
Awaiting s 24 V power supply
H1
Awaiting start of auto-programming
H2
Auto-programming mode - opening
H4
Auto-programming mode - closing
F0
Awaiting remote control memorisation for operation in complete opening mode
F1
Awaiting remote control memorisation for operation in pedestrian opening
mode
F2
Awaiting remote control memorisation for remote lighting control
F3
Awaiting remote control memorisation for auxiliary output control
Code
Description
Solution?
E1
Cell safety autotest fault
Check the “P07” parameter setting. Check
the wiring of the cells.
E2
Programmable safety autotest
fault
Check the “P09” parameter setting. Check
the programmable safety input wiring.
E4
Obstacle detection when opening
E5
Obstacle detection when closing
E6
Cell safety fault
Check that no obstacles are causing the
cells or safety edge to detect.
Check that "P2" is correctly configured
in relation to the device connected to the
safety input.
Check the safety device wiring.
Check that the photoelectric cells are
correctly aligned.
E8
Programmable safety fault
E9
Thermal protection
E10
Motor short circuit protection
Check the motor wiring.
E11
24V power supply short protection Check the wiring of the peripherals connect-
ed to terminals 21 to 26 then disconnect the
power supply for 10 seconds.
N.B.: maximum accessories consumption
= 1.2 A
E12
Hardware fault
Request a gate movement. If the fault is still
present, contact Somfy.
E13
Accessories power supply fault
N.B.: maximum accessories consumption
= 1.2 A
Check the consumption of the connected
accessories.
E14
Intrusion detection
Normal operation (attempted intrusion,
current reinjection activated, etc.)
E15
Fault when the control box
supplied by the backup battery is
first switched on
Disconnect the backup battery and connect
the control box to the mains to switch it on
for the first time.
Code
Description
Code
Description
C1
Awaiting command
C12
Current reinjection in progress
(Control Box 3S Axovia only)
C2
Gate opening
C13
Safety device autotest in progress
C3
Awaiting gate closure
C14
Permanent complete opening wire
control input
C4
Gate closing
C15
Permanent pedestrian opening
wire control input
C6
Detection in progress for cell
safety
C16
BUS cell programming refused
C8
Detection in progress for program-
mable safety
Cc1
9.6 V power supply
C9
Detection in progress for emer-
gency stop safety
Cu1
24 V power supply
ACCESSING MEMORISED DATA
To access memorised data, select parameter "Ud" then press "OK".
Data
Description
U0 to U1
Overall complete opening cycle counter
U2 to U3
Complete opening cycle counter since last auto-programming
U6 to U7
Cycle counter with overall obstacle detection
U8 to U9
Cycle counter with obstacle detection since the last auto-programming
U12 to U13 Partial opening cycle counter
U14 to U15 Reset movement counter
U20
Number of remote controls memorised for complete opening control
U21
Number of remote controls memorised for pedestrian opening control
U22
Number of remote controls memorised for remote lighting control
U23
Number of remote controls memorised for auxiliary output control
U24
0 = no system key present, 1 = system key present
d0 to d9
Log of the last 10 faults (d0 most recent - d9 oldest)
dd
To clear the fault log: press and hold "OK" for 7 s.