Installation
and
Operation
Manual
(REV
H)
PVI
6500
/
PVI
7500
68
Noise
level
at
full
load
<
47db(A)
at
1m
Mechanical
Outdoor
enclosure
NEMA
3R,
Rainproof
Cooling
Cooling
fan
DC
Input
terminals
Accepts
wire
size
of
#10
to
#6
AWG
AC
Output
terminals
Accepts
wire
size
of
#10
to
#6
AWG
DC
conduit
connection
access
1”
knockout
(1.38")
/
¾”
knockout
(1.06")
AC
conduit
connection
access
1”
knockout
(1.38")
/
¾”
knockout
(1.06")
Communication
connection
¾”
knockout
(1.06")
/
½”
knockout
(0.79")
Mechanical
Weight
/
Shipping
weight
41
kg
/
47
kg
(90
lb
/
104
lb)
Dimensions
(HxWxD)
28.8
x
17.2
x
8.2"
(732
x
438
x
208
mm)
Shipping
dimensions
(HxWxD)
33.1
x
21.65
x
13.98"
(840
x
550
x
355
mm)
Communication
Interface
Communication
RS232
and
RS485
Communication
protocol
MODBUS
LCD
display
Yes
LED
indicators
Red
/
Green
/
Yellow
Positive
ground
inverters
Name
‐
Part
number
PVI
6500
PVI
7500
Model
name
PVI
6500
‐
PG
PVI
7500
‐
PG
Certifications
UL
1741,
FCC
Part
15
B,
IEEE
1547,
IEEE
C62.41.2,
IEEE
C37.90.1,
CSA22.2#107.1
*
Factory
settings
can
be
adjusted
with
the
approval
of
the
utility.
This
unit
is
provided
with
adjustable
trip
limits
and
may
be
aggregated
above
30kW
on
a
single
Point
of
Common
Coupling.
Adjustable
voltage,
Frequency
and
Reconnection
Settings
Setting
Range
Default
Accuracy
Over
‐
voltage
(%)
108.75~110
110
±1
Under
‐
voltage
(%)
85~90
88
±1
Over
‐
voltage
Reconnect
voltage*
(%)
105.83~110
105.83
±1
Under
‐
voltage
Reconnect
voltage*
(%)
85~91.67
91.67
±1
Over
‐
frequency
(Hz)
60.4~61
60.49
±0.02
Under
‐
frequency
(Hz)
57~59.8
59.31
±0.02
Over
‐
voltage
clearing
time
(cycle)
59~120
59
±1
Under
‐
voltage
clearing
time
(cycle)
119~300
119
±1
Over
‐
frequency
clearing
time
(cycle)
9~12
9
±1
Under
‐
frequency
clearing
time
(cycle)
9~18000
9
±1
Setting
Range
Default
Accuracy
AC
high
‐
voltage
limit
(%)
100~110
109
±1
Reconnect
delay**
(s)
10~600
20
±0.01
*
The
default
values
are
within
the
Range
B
of
ANSI
C84.1
**
Once
a
grid
failure,
the
inverter
waits
300
seconds
before
the
next
connection
to
the
grid.