Installation
and
Operation
Manual
(REV
H)
PVI
6500
/
PVI
7500
50
assistance
if
the
range
needs
to
be
adjusted
VacL2
L
The
voltage
between
L2
and
neutral
is
under
the
lower
limit.
‐
Verify
setting
for
S201
is
correct
for
the
grid
voltage
applied
‐
Measure
the
AC
voltage
and
compare
to
the
voltage
on
the
inverter
display
‐
Contact
Solectria
Renewables
for
assistance
if
the
range
needs
to
be
adjusted
MOV
Fault,
AC
High
voltage
protection
function
failed
on
the
AC
side.
‐
Verify
MOV
appearance
is
OK
‐
Contact
Solectria
Renewables
MOV
Fault,
DC
High
voltage
protection
function
failed
on
the
DC
side.
‐
Verify
MOV
appearance
is
OK
‐
Contact
Solectria
Renewables
GFDI
The
GFDI
Fuse
is
open
or
blown.
‐
Use
DMM
to
verify
GFDI
is
open
contact
installing
company
to
inspect
and
repair
the
array
‐
Replace
fuse
with
same
type
and
rating
DCInjectCurH
Too
much
DC
current
injected
into
the
AC
grid
is
detected.
‐
Turn
off the
inverter
and
restart.
‐
If
the
error
re
‐
occurs
Contact
installing
company
or
Solectria
Renewables
VdcbusH
Internal
DC
bus
voltage
is
above
the
upper
limit.
‐
Turn
off the
inverter
and
restart.
‐
If
the
error
re
‐
occurs
Contact
installing
company
or
Solectria
Renewables
Internal
COMM
Internal
communication
failed.
‐
Turn
off the
inverter
and
restart.
‐
If
the
error
re
‐
occurs
Contact
installing
company
or
Solectria
Renewables
Watchdog
Internal
watchdog
function
triggered.
‐
Turn
off the
inverter
and
restart.
‐
If
the
error
re
‐
occurs
Contact
installing
company
or
Solectria
Renewables
Idc
Test
Offset
check
for
grid
monitoring
failed
‐
Turn
off the
inverter
and
restart.
‐
If
the
error
re
‐
occurs
Contact
installing
company
or
Solectria
Renewables
Offset
The
DC
injection
current
monitoring
function
failed.
‐
Turn
off
the
inverter
and
restart.
‐
If
the
error
re
‐
occurs
Contact
installing
company
or
Solectria
Renewables
Temp.
Sensor
Offset
check
for
grid
monitoring
failed.
‐
Turn
off the
inverter
and
restart.
‐
If
the
error
re
‐
occurs
Contact
installing
company
or
Solectria
Renewables
RAM
Test
The
internal
temperature
sensor
failed.
‐
Turn
off the
inverter
and
restart.
‐
If
the
error
re
‐
occurs
Contact
installing
company
or
Solectria
Renewables
EEPROM
Test
Memory
failed
‐
Turn
off the
inverter
and
restart.
‐
If
the
error
re
‐
occurs
Contact
installing
company
or
Solectria
Renewables
System
Error
EEPROM
test
failed.
‐
Turn
off the
inverter
and
restart.
‐
If
the
error
re
‐
occurs
Contact
installing
company
or
Solectria
Renewables
Version
Error
The
system
failed.
‐
Turn
off the
inverter
and
restart.
‐
If
the
error
re
‐
occurs
Contact
installing
company
or
Solectria
Renewables
CPU
Delta
Fac
CPU
Delta
Vac
CPU
Delta
GFDI
CPU
Delta
Idc
The
firmware
version
is
not
correct.
Internal
measurement
comparison
error
or
defective
hardware
‐
Turn
off the
inverter
and
restart.
‐
If
the
error
re
‐
occurs
Contact
installing
company
or
Solectria
Renewables