Installation
and
Operation
Manual
(REV
H)
PVI
6500
/
PVI
7500
49
assistance
if
the
range
needs
to
be
adjusted
VacL
The
AC
voltage
of
main utility
is
below
the
lower
limit.
‐
Verify
setting
for
S201
is
correct
for
the
grid
voltage
applied
‐
Measure
the
AC
voltage
and
compare
to
the
voltage
on
the
inverter
display
‐
Contact
Solectria
Renewables
for
assistance
if
the
range
needs
to
be
adjusted
FacH
The
frequency
of
AC
voltage
of
the
utility
is
above
the
upper
limit.
‐
Measure
the
frequency
and
compare
to
the
frequency
on
the
display
‐
Contact
Solectria
Renewables
for
assistance
if
the
range
needs
to
be
adjusted
FacL
The
frequency
of
AC
voltage
of
the
utility
is
below
the
lower
limit.
‐
Measure
the
frequency
and
compare
to
the
frequency
on
the
display
‐
Contact
Solectria
Renewables
for
assistance
if
the
range
needs
to
be
adjusted
VpvH
The
DC
voltage
of
PV
array
is
above
the
upper
limit.
‐
Turn
off
the
inverter
disconnect
‐
Measure
the
VDC
at
the
Inverter
disconnect
if
over
599VDC
the
solar
array
needs
to
be
inspected
‐
Contact
installing
company
‐
Do
not
turn
on
the
inverter
until
the
condition
is
repaired
Imax_AC
Over
current
on
the
AC
side.
‐
The
inverter
will
continue
to
operate
at
a
lower
current
‐
If
message
occurs
frequently
contact
the
installing
company
InvTempMax
The
internal
temperature
of
the
inverter
exceeded
the
safe
operating
limit.
‐
If
the
inverter
is
located
in
direct
sunlight
it
may
need
to
be
shaded
‐
The
VDC
input
may
be
too
high
causing
increased
temperature,
reduce
VDC
input.
‐
Contact
installing
company
or
Solectria
Renewables
Relay
Open
Relay
Close
Relay
test
failed.
‐
Contact
installing
company
or
Solectria
Renewables
VacL1
H
The
voltage
between
L1
and
neutral
is
over
the
upper
limit.
‐
Verify
setting
for
S201
is
correct
for
the
grid
voltage
applied
‐
Measure
the
AC
voltage
and
compare
to
the
voltage
on
the
inverter
display
‐
Contact
Solectria
Renewables
for
assistance
if
the
range
needs
to
be
adjusted
VacL1
L
The
voltage
between
L1
and
neutral
is
under
the
lower
limit.
‐
Verify
setting
for
S201
is
correct
for
the
grid
voltage
applied
‐
Measure
the
AC
voltage
and
compare
to
the
voltage
on
the
inverter
display
‐
Contact
Solectria
Renewables
for
assistance
if
the
range
needs
to
be
adjusted
VacL2
H
The
voltage
between
L2
and
neutral
is
over
the
upper
limit.
‐
Verify
setting
for
S201
is
correct
for
the
grid
voltage
applied
‐
Measure
the
AC
voltage
and
compare
to
the
voltage
on
the
inverter
display
‐
Contact
Solectria
Renewables
for