RVS-AX

 

 

 

 

 

Instruction and Commissioning Manual

 

 

 

www.solcon.com

  

              

RVS-AX

Analog

Low Voltage Soft Starter

8-170 A , 220-600V

 

 

Low Voltage Analog Soft Starter

 

 

Ver. 1009

Summary of Contents for RVS-AX

Page 1: ...RVS AX Instruction and Commissioning Manual www solcon com RVS AX Analog Low Voltage Soft Starter 8 170 A 220 600V Low Voltage Analog Soft Starter Ver 1009...

Page 2: ...3 Heatsink over temperature protection 6 3 6 4 Fault Logic and Reset Circuits 7 3 7 Starter selection tables for various voltage ratings 7 3 7 1 Ordering Information 8 4 Recommended Wiring Schemes 9 4...

Page 3: ...liance with IEC 947 4 2 for class A equipment 2 Use of the product in domestic environments may cause radio interference in which case the user may be required to employ additional mitigation methods...

Page 4: ...e RVS AX 3 2 Rating and frames sizes 3 3 Starter Selection Select the starter according to motor s Full Load Ampere FLA as indicated on its nameplate even if the motor will not be fully loaded The RVS...

Page 5: ...inal is of no use Leave this terminal not connected 3 4 5 End Of Acceleration terminals 5 6 Voltage free N O 8A 250VAC 1800VA max The contact closes after the time adjusted on the Ramp Up potentiomete...

Page 6: ...ase Loss The protection becomes operational when the starter is energized It protects the motor from single phasing It will trip the starter when one phase is missing for more than 1 sec When this pro...

Page 7: ...e upstream contactor Mains voltage will be disconnected thus resetting the RVS AX and the motor will restart instantaneously see Fault Resetting 3 7 Starter selection tables for various voltage rating...

Page 8: ...44 58 72 85 105 145 170 Mains Voltage Specify Description 230 220 240 Vac 10 15 400 380 415 Vac 10 15 440 440 Vac 10 15 480 460 500 Vac 10 15 600 575 600 Vac 10 15 Options Specify Description 0 No op...

Page 9: ...g Notes WARNINGS When mains voltage is connected to the RVS AX full voltage may appear on the starter load terminals Therefore for isolation purposes it is necessary to connect an isolating device bef...

Page 10: ...AX 17 2 000 6 6 URS 45 RVS AX 31 3 000 6 6 URS 63 RVS AX 44 6 000 6 6 URB 100 RVS AX 58 12 000 6 6 URB 150 RVS AX 72 18 000 6 6 URB 160 RVS AX 85 40 000 6 6 URD 200 RVS AX 105 60 000 6 6 URD 250 RVS A...

Page 11: ...11 Dimensions ________________________________________________________________________________________________ 5 DIMENSIONS RVS AX 8 17 31 44 Note Mains voltage terminals 16mm2 RVS AX 58 72...

Page 12: ...12 Dimensions ________________________________________________________________________________________________ RVS AX 85 105 RVS AX 145 170...

Page 13: ...elow the starter for suitable airflow It is recommended to mount the starter directly on the rear metal plate for better heat dissipation Do not mount the starter near heat sources Surrounding air tem...

Page 14: ...igned for the higher heat dissipation Internal enclosure heating can be reduced through the use of additional ventilation 6 4 1 44BHeat dissipation during RUN of RVS AX8A and RVS AX17A No internal byp...

Page 15: ...ometers settings Potentiometer Range Description Motor FLC 50 100 The adjustment allows easy setting of the RVS AX current level automatically adjusting current based functions Overload Current Limit...

Page 16: ...s highest current during starting Range is 100 400 of FLC as set on motor s FLC adjustment Too high of a setting will allow higher currents to be drawn from mains resulting in faster acceleration Too...

Page 17: ...RESET button Green On Will lit when Mains voltage is connected to the starter Yellow Ramp Up Down Will lit during soft start and soft stop process indicating that motor supply voltage is ramping up or...

Page 18: ...isolating device before upstream the starter 2 Power factor correction capacitors must not be installed on starters load side When required install capacitors on starter s line side 3 Before starting...

Page 19: ...ter line terminals On LED will light 4 Apply Start command Motor starts to turn shortly after Start Initial inrush current or mechanical shock is too high Increase Initial Voltage and start again Decr...

Page 20: ...moothly decreasing to the operating current High inertia loads crushers centrifuges mixers etc In these cases actual current is at Current limit setting in part of the starting time Current Limit set...

Page 21: ...e overload level and thermal register has filled up Check FLA FLC and Overload settings check motor current wait at least 15 minutes to let motor and starter cool down before restarting Phase Loss LED...

Page 22: ...Model Number And Build Options Example 170 400 8 S RVS AX _ _ _ _ _ _ __ _ Serial Number Purchasing Date Sale Installation Date Failure Date Draw one line diagram Draw control diagram Define time of...

Page 23: ...the starter after the fault has been removed Indications Indication lights LEDs ON Green Lights when three phases are connected to the RVS AX Ramp Up Ramp Down Yellow Lights upon start signal or durin...

Page 24: ...________________________ Mechanical Shock resistance 8 gn Conforming to EN 60947 4 2 Vibration resistance 2 gn Conforming to EN 60947 4 2 Output relay End of Acceleration Contact N O 8 A 250 V Fault C...