23 • Technical Specifications
________________________________________________________________________________________________
10.
TECHNICAL SPECIFICATIONS
Environment
Supply voltage
230
220 - 240 Vac +10% -15%
400
380 - 415 Vac +10% -15%
440
440 Vac +10% -15%
480
460 - 500 Vac +10% -15%
600
575 - 600 Vac +10% -15%
Frequency
50 / 60 Hz
Load
Three-Phase, Three-Wire, Squirrel
Cage Induction Motor
Degree of protection
RVS-AX 8-44A: IP 20
RVS-AX 58-170A: IP 00
Altitude
1000 m above sea level
Consult factory for derating
Adjustments
FLC (Full Load Current)
50% - 100%
Starting Torque (Initial Voltage) 10-50 % of full voltage
Current limit
100 % - 400% of nominal current
Ramp Up Time (soft start)
2 - 30 sec.
Ramp Down Time (Soft Stop)
0.2 - 30 sec.
Protection
Electronic Overload
Inverse time (I
2
t), factory preset at 115% of FLC, active only during
Run.
Phase Loss
Trips when one phase is missing (When Neutral is connected)
Heatsink Over temperature
Trips when the heatsink temperature exceeds 85ºC.
Reset buttons
To reset the starter, after the fault has been removed.
Indications
Indication lights (LEDs)
ON - Green
Lights when three phases are
connected to the RVS-AX.
Ramp Up / Ramp Down –
Yellow
Lights upon start signal or during soft
stopping.
RUN – Green
Lights upon end of starting. When
the internal bypass relays close.
No internal bypass in RVS-AX8A &
RVS-AX17A
Overload – Red
Inverse time electronic overload
becomes operational after the End
Of Acceleration process.
Phase loss – Red
Lights when one or two phases are
missing for more than 1 sec.
Over temperature – Red
Lights on and trips the starter when
the heatsink temperature rises
above 85ºC.
Temperatures
Operating
-10° to 40°C
Storage
-20° to 70°C
Relative humidity
93 % - non condensed
EMC
Immunity to radio electric
interference
EN 1000-4-3 level 3
Conforming to EN 60947-4-2
Electrostatic discharge
EN 1000-4-2 level 3
Conforming to EN 60947-4-2
Immunity to electrical
transients
EN 1000-4-4 level 4
Conforming to EN 60947-4-2
Shock waves of voltage /
current
EN 1000-4-5 level 3
Conforming to EN 60947-4-2
Radiated and conducted
emissions
EN 1000-4-6 level 3
Radio frequency emissions
According to EN 55011 class A Conforming to EN 60947-4-2