Electrical Connection
Electrical Connection
Battery breaker requirements
A 1 - H y b r i d
Series Inverter
Nonpolarized
DC Breaker
Battery
BAT Port
CAUTION!
The installer is responsible for providing overcurrent protection.
To reduce the risk of fire, install a circuit breaker or overcurrent
device on both po) and negative(-) conductors to protect the
system.
WARNING!
Battery circuit not isolated from PV
input.
Ø
Terminals
Required Torque
Permitted Wire Size
BMS Terminal
Type
RJ45
Plug-in
RJ45, 8-conductor
CAT5 non-crossover
BMS terminal connection
The communication interface between inverter and battery is made possible via
CAN with a RJ45 connector. The PIN definition is shown as below.
GND
GND
GND
CAN_H
1
2
3
4
5
6
7
8
1
8
CAN_L
Ø
A1-Hybrid-6.0-US
Inverter Model
35A, 600 Vdc, 35KA
Recommended DC Breaker Model
A1-Hybrid-7.0-US
A1-Hybrid-7.6-US
A1-Hybrid-8.6-US
Max. BAT Output Current
25A
25A
25A
25A
35A, 600 Vdc, 35KA
35A, 600 Vdc, 35KA
35A, 600 Vdc, 35KA
There are ten ports on the Bus-Bar. Any one of them can be connected with
the earth wiring. The earth wiring shall be connected to the exterior Bus-Bar
6.6 Ground Connection
Ø
Required torque
Max.12 lbf-in
Terminals
Wire size permitted
Ground Bus-bar
8AWG,600V,194
℉
(90
℃
)
for A1-Hybrid-6.0/7.0-US
6AWG,600V,194
℉
(90
℃
)
for A1-Hybrid-7.6/8.6-US
Ground Wiring Connection
Note for specific wiring requirements, refer to Section 6.1.
For specific wire size and torques, refer to Section 6.1.
X
485A
485B
A nonpolarized DC breaker is required to make sure that the battery can be
securely disconnected with from the inverter when needed.
Refer to the table below to determine the appropriate DC breaker size. The DC
load breaker selection and installation must follow the National Electrical
Code (NEC), ANSI/NFPA 70 or local electrical codes.
User can additionally earth the inverter to the enclosure of a second
earthing or equipotential bonding if it is required by local safety. This
prevents electric shock if the original protective conductor fails.
34
35