Electrical Connection
Electrical Connection
6.1 Overview Of All Electrical Wirings Method
All electrical wiring will be done in the wiring box, and all electrical wiring
methods are similar. Therefore this section will introduce all electrical
wiring steps and requirements.
Removing the wiring box cover
Ø
Required wire size and torques
Ø
Part
Required torque
Max.23 Ibf-in
Note for specific wiring requirements, refer to Section 6.1.
For specific wire size and torques, refer to Section 6.1.
Removing wiring box waterproof plugs
Ø
A1-Hybrid series inverter has 9 1G holes and 2 3/4G holes for wiring connection.
The 9 1G holes are used for electrical wiring connection, 2 3/4G holes are used for
communication connection.
9 1G waterproof plugs and 2 3/4G waterproof plugs has been installed on inverter
at the factory.
Before wiring connection, these waterproof plugs should be removed by the
operator.
Step 1: Remove the waterproof plugs by placing a flat blade screwdriver in the slot
on the waterproof plug face and turning while gripping the nut on the inside of the
enclosure to ensure it does not slip.
Step 2: Unscrew the nut from the waterproof plug and slip the conduit plug out of
the waterproof opening.
Conduit installation and wiring routing
Ø
Part
Required torque
Max.1.4 Ibf-in
Part
Required torque
Install Conduit Fitting
Max.1.4 Ibf-in
Note for specific wiring requirements, refer to Section 6.1.
For specific wire size and torques, refer to Section 6.1.
Note for specific wiring requirements, refer to Section 6.1.
For specific wire size and torques, refer to Section 6.1.
1G
1G
1G
1G
1G
1G
1G
3/4G
3/4G
1G
Terminals
Required Torque
Permitted Wire Size
PV Terminals
Battery Terminals
Grid Terminals
EPS Terminals
Grounding Block
Part
Required Torque
Removing Wiring Box Cover Screw
Removing Conduit Fitting
Max. 23 lbf-in
Max. 13.8 lbf-in
14AWG,600V, 194
℉
(90
℃
)
10AWG,600V, 194
℉
(90
℃
)
Plug-in
Max. 11.5
lbf-in
8AWG, 600V, 194
℉
(90
℃
) for
A1 Hybrid-6.0/7.0-US
6AWG, 600V, 194
℉
(90
℃
)
for
A1 Hybrid-7.6/8.6-US
Autotransformer Terminals
Plug-in
Plug-in
Step 1: Turn DC switch in “OFF” position. Note that the cover cannot be
removed when the DC switch is in “ON” position.
Step 2: Remove the 8 cover screws, then remove the cover.
Removing Wiring Box Cover Screw
Removing Waterproof Plugs
Operator should use the standard size conduits and plugs which must fit with the
holes on the bottom of the inverter. Conduit fittings need to be water tight, and
an insulated type is preferred.
Once conduit and fittings are installed, wires should go through the conduit and
be locked into the corresponding terminals (refer to next section for details).
22