Electrical Connection
Electrical Connection
A1-Hybrid Series inverter can be connected with PV modules in series with
2 MPPTs for 6.0KW, 3 MPPTs for 7.0KW and 7.6KW , 4 MPPTs for 8.6KW.
PV String Connection
For the A1-Hybrid-8.6 inverter,
4 strings need to be connected
as shown in the picture to the
right.
For the A1-Hybrid-7.6 and inverter
and the A1-Hybrid-7.0 inverter,
3 strings need to be connected
as shown in the picture to the
right.
For the A1-Hybrid-6.0 inverter,
2 strings need to be connected
as shown in the picture to the
right.
Note for specific wiring requirements, refer to
Section 6.1.
For specific wire size and torques, refer to Section 6.1.
Ø
Terminals
Wire size permitted
PV terminals
14AWG,600V,194
℉
(90
℃
)
6.3 Grid Connection
The connection procedure will vary depending on the grid configuration.
The following table provides an overview of the compatible grid configurations, of
which voltage limit, frequency limit and conductors have to be connected to the
inverter to comply with the grid configuration.
CAUTION!
The installer is responsible for providing overcurrent protection.
To reduce the risk of fire, connect only to a circuit provided with 63A
maximum branch-circuit overcurrent protection in accordance with
the National Electrical Code, ANSI/NFPA 70.
Public grid configuration allowed:
L1
L2
N
240V/120V Split Phase AC Grid
240V 180
L1
L2
N
240V/120V Stinger AC Grid
240V 120
240V 120
240V 120
Ø
Grid terminal connection
Ø
CAUTION!
DANGER — HIGH VOLTAGE!
Note for specific wiring requirements, refer to Section 6.1.
For specific wire size and torques, refer to Section 6.1.