![Solartron Mobrey 7828 Technical Manual Download Page 73](http://html1.mh-extra.com/html/solartron-mobrey/7828/7828_technical-manual_1314071073.webp)
78285000_AA
B-1
B
Calculated Parameters
B.1 INTRODUCTION
The 7828 Density Transmitter is capable of calculating a number of parameters based on
the measured line density and temperature. These calculated parameters are often
referred to as ‘special functions’. Only one calculated parameter is available at any one
time; it can be used to control the analog (4-20mA) output, and can also be accessed as a
digital value (Modbus Register 260).
This section describes the algorithms used in these calculations.
The availability of the calculated parameters is dependent on whether Matrix or API is
chosen as the density referral method.
Special Function
API referral
Matrix referral
Specific Gravity
✔
✔
API°
✔
% mass
✔
% volume
✔
° Baumé
✔
° Brix
✔
User defined quadratic
✔
None
✔
✔
Summary of Contents for 7828
Page 1: ...Precision measurement solutions 7828 Density Transmitter TECHNICAL MANUAL 78285000 ...
Page 4: ...7828 Density Transmitter Technical Manual iv 78285000_AB ...
Page 10: ...7828 Density Transmitter Technical Manual x 78285000_AB ...
Page 60: ...Calibration check 7828 Density Transmitter Technical Manual 5 6 78285000_AA ...
Page 66: ...Maintenance 7828 Density Transmitter Technical Manual 6 6 78285000_AA ...
Page 72: ...Specification 7828 Density Transmitter Technical Manual A 6 78285000_AB ...
Page 80: ...Calculated parameters 7828 Density Transmitter Technical Manual B 8 78285000_AA ...
Page 82: ...7828 Density Transmitter Technical Manual Safety Certification C 2 78285000_AC ...
Page 106: ...7828 Density Transmitter Technical Manual COSHH Document F 2 78285000_AA ...
Page 108: ...7828 Density Transmitter Technical Manual COSHH Document F 4 78285000_AA ...
Page 109: ......