Appendix E: Maintenance and replacement of the fan
SolarEdge Installation Guide - MAN-01-00060-2.6
75
Appendix E: Maintenance and Replacement
fan
The three-phase inverter has two fans, one internal and requires a SolarEdge technician to replace it (fan 1) and the other
is accessible from the outside of the inverter (fan 2). A replacement kit is available from SolarEdge.
Figure 35: Fan inverter 2
Fan Interview
1
Maintain the fan and the screen clean by blowing out the dust accumulated, or at least one
1
Maintain the fan and the screen clean by blowing out the dust accumulated, or at least one
annually.
2
Check the screen the status of the fan status on the LCD (refer to
Status status
2
Check the screen the status of the fan status on the LCD (refer to
Status status
2
Check the screen the status of the fan status on the LCD (refer to
Status status
3
If any of the following events occurs, replace the fan as described below:
3
If any of the following events occurs, replace the fan as described below:
•
When the fan stops working
•
Fan Status indicates
Born does not work ;
before replacing the fan, turn off the AC inverter and check if the
Fan Status indicates
Born does not work ;
before replacing the fan, turn off the AC inverter and check if the
Fan Status indicates
Born does not work ;
before replacing the fan, turn off the AC inverter and check if the
Fan Status indicates
Born does not work ;
before replacing the fan, turn off the AC inverter and check if the
status is cleared
status is cleared
•
The following error message appears:
V entilateur 2 enpanne
Fan replacement 2
1
Place the ON / OFF switch of the inverter OFF and wait until the LCD shows
1
Place the ON / OFF switch of the inverter OFF and wait until the LCD shows
that the DC voltage is safe (<50 V), or wait five minutes before proceeding to the next step.
WARNING !
If you do not see the inverter panel, or if a fault is indicated on the LCD, wait five minutes for the inverter input capacitors discharge.