27
Settings manual
Required room temperature is set on 6 °C by default and can be changed in service
parameter S1.11.
SETTING THE REQUIRED NIGHT TEMPERATURE
CONTROLLER PARAMETERS > BASIC PARAMETERS >
REQUIRED NIGHT TEMPERATURE
FROST PROTECTION SETTING
When the heating is turned off or it is not necessary, the controller turns off the boiler. By
existing danger of freezing the boiler is automaticaly turned on, if the outdoor temperature
drops bellow the setted frost protection temperature. Default setting is 2 °C and can be set in
span between –20 and 10 °C.
The required night temperature can be viewed, by choosing:
Frost protection can be set by choosing:
CONTROLLER PARAMETERS > BASIC PARAMETERS >
FROST PROTECTION
SETTING THE REQUIRED DAY TEMPERATURE
The required day temperature can be viewed, by choosing:
CONTROLLER PARAMETERS > BASIC PARAMETERS >
REQUIRED DAY TEMPERATURE
BASIC PARAMETERS
SUMMER/WINTER SWITCHOVER TEMPERATURE SETTING
The controller has a built-in function, which automaticaly turns the heating off, if the average
24h temperature is higher than the setted summer/winter switchover temperature. The hea-
ting is turned on again, when the average 24 h temperature drops bellow the setted
switchover temperature. If the operation mode switch is in position »day temperature«, than
the described function is deactivated. Default setting is OFF and can be set in span between
10 and 30 °C, OFF.