PRODUCT INFORMATION
Wood log boiler HVS
Main
tenance
adjusting the secondary air
assembly group
forced draft
fan
For a good combustion you should try to achieve an
oxygen proportion of approx. 5,5%. This is controlled
by secondary air.
Adjusting the secondary air:
‐ Loosen the lock nuts at the screws
‐ turn screws clockwise as far as it is possible
‐ turn screws anti‐clockwise for 2 or 3 turns.
(reference values ‐ exact adjustment in accordance
with local conditions [chimney draft ...]).
The adjustments have to be repeated after each
demounting and remounting of the assembly group!
Adjusting the secondary air (only with HVS E)
Forced draft fan
The forced draft fan is mounted on the fan carrier sheet.
The boilers HVS 16, 25 and 40 have one forced draft fan, and the HVS
60 and 100 have two fans.
The forced draft fan consists of 4 components: forced draft fan body;
motor; capacitor; fan wheel.
Note:
A clean and dust‐free environment is the basis for a reliable ope‐
ration of the fan. Dirt on the wings causes loud operation and leads to
a changing of the parameters. Thus, a clean combustion is no longer
guaranteed. The fan wings should be cleaned from time to time.
assembly
group
carrier
sheet
Disconnect boiler form the mains supply before removing the casing.
Never touch conducting devices – danger to life exists!
The secondary air has to be adjusted before the boiler’s initial operation and, if necessary, adapted to the
given chimney conditions (only with HVS E).