SYSTEM SETUP AND OPERATION GUDIE FOR THE 1 kW HYBRID POWER SYSTEM (HPS)
PRELIMINARY DRAFT
GROUP 1: CHARGE CURVE
Parameter
Parameter Value
Description
BULK CURRENT
20 A
Sets the maximum charging current during the Bulk Charging Stage.
ABSORP VOLTAGE
29.0 V
Sets the charging voltage in the Constant Voltage Absorption Stage.
EQUALIZE VOLTAGE
29.0 V
Not applicable when using LiFePO
4
batteries.
FLOAT VOLTAGE
29.0 V
Sets the charging voltage in the Constant Voltage Float Stage.
COMPENSATE
-3mV /°C/Cell
Sets the temperature compensation for the battery.
BATT OVER VOLT
(Shut Down)
32.0 V
Sets the upper battery voltage threshold at which inverting/charging
operations are switched off to protect the PRO-Verter.
RESET VOLTAGE
(Low Voltage Reset)
29.0 V
The PRO-Verter inverter will restart when the battery voltage rises to
this set value or above after “Battery low voltage!” shutdown occurs.
LOW VOLT ALARM
25.6 V
Battery voltage at which the “Alarm” triggers AGS to start generator.
BATT LOW VOLTAGE
24 V
Sets the battery low voltage threshold at which the PRO-Verter inverter
will shut down to protect the battery from overdischarge.
LV DETECT TIME
60 sec
This is the timer for shutting off the inverter. Battery voltage must be at
the low voltage set point for this period of time before the inverter shuts
off.
LV CUT OFF TIME
3600 sec
This timer shuts off everything including the charger.
(The load on the inverter will already be cut off during this time.)
EQUALIZE-4STAGES
0=NO
Equalize disabled with LiFePO
4
batteries.
ONLINE MODE
0 = Option 1 (Default)
Offline
0 = Normal…AC input priority (Off-Line)
1 = On-Line…Inverter priority
2 = Charger Only…Charging & AC bypass - only, no inverting
RESET TO BULK
25.6 V
Sets battery voltage at which the charger will terminate current charging
stage of the selected Charging Profile and restart charging from the
beginning.
GS DETECT TIME
60 sec
A timer that sets the duration the battery voltage has to remain at
threshold of Low Volt Alarm or lower before generator auto start/stop.
GEN ON TIME
30 minutes
N/A as programmed
GEN OFF DELAY
1 minute
Must be in the generator-stop condition for 1 minute before opening
the relay
ABSORP TIME
10 min
ABSORP EXIT AMPS
6 A
Set to ~1-% of battery bank capacity.) Value not in play with 2 Stage
Type 1 charging
CHARGING PROFILE
3 = 2 Stage Type 1
(mimics CC/CV-type charging)
Charge Curve Programmable Settings
Parameters in this group define System battery charging protocols.
Table 4. Parameters for Battery Charging/Battery Protection
Continued on following page.
Please contact Solar Stik Technical Support before changing settings other than the clock or
the AC Input settings These settings are highlighted orange in the tables that follow