SYSTEM SETUP AND OPERATION GUDIE FOR THE 1 kW HYBRID POWER SYSTEM (HPS)
PRELIMINARY DRAFT
a Connect PRO-Verter to Energy Storage Modules
Figure 15. PRO-Verter to ESM connection
24VDC PRO-Verter S 2000
24VDC Li Expander Pak 1300s
24VDC Inter-Connect Strip 7
Note:
A variety of energy storage modules (ESMs) may be connected to the PRO-Verter. Never
mix battery chemistries in a System.
1. Connect the (4 AWG) Linear Inter-Connect Cable straight-plug to the Expander Pak. The plug and
socket are polarized (Figure 15A) and can be connected only in the proper orientation.
2. After inserting the plug into the socket (Figure 15B), twist the knob to lock the connection.
Note:
The red wire cover denotes the positive (+) terminal, and green (or black) denotes the
negative (-) terminal.
+
–
A
B
The 24VDC Expander Pak 1300 normal operating voltage ranges from 21.0 VDC to 29.0 VDC. Prior
to operating the Expander Pak for the first time, charge it fully. Recharge it with connection to a
PRO-Verter, Power Hub, or an external charging source, such as a battery charger, until the battery
reaches 100% SOC.
3. Connect the “angled” Inter-Connect plug to the Inter-Connect Strip 7. Use a standard Inter-
Connect cable with two (2) angled ends to connect the Inter-Connect Strip to the PRO-Verter
Expander Pak only Inter-Connect port.
Straight
Plug
Angled
Plug
*
* 13-1000267 Linear
*
**
** 13-1000032 Standard