87
February 2020
|
Solar Stik
®
, Inc.
System Setup and Operation Manual for ATSC MS3 L0
PRO-Verter High-temp Generator Auto-Start
When a heavy load (≥100% rated output) is placed on the PRO-Verter while inverting, the internal
transformer temperature will rise in accordance with the amount of power it is processing. If
the internal “Transformer Temperature” reaches or exceeds 221 ºF (105 ºC) the PRO-Verter will
automatically start a connected generator to assume the load. This protects the PRO-Verter from
damage and/or going into FAULT mode and provides continuity of operations during peak demand.
This feature has been programmed at the factory and requires no programming by the operator
other than the duration of the generator run time (based on the generator fuel tank volume), if the
time needed is different than what is pre-programmed.
Should the PRO-Verter go into fault mode (Overtemp or TmfrOvertemp) during peak demand, ensure
that the AGS is set to Auto (FAVS 5 Menu) and that Set Gen Run Temp is set to “1.0 Hrs” (If this
option is available) by following the Menu Map below:
Set Gen Run Temp
Off
Set Gen Run Temp
Time = 1.0 Hrs
04E Gen Run Temp
SETUP
Status
04 AGS Setup
Set Gen Run Temp
Start=Ext. Input
press to turn
“on”
press select;
scroll to appropriate
time
scroll to “on”;
press select
default setting.
If not set,
choose 1.0 Hrs
(option may not
be available)
Note
: Do not change Max Gen
Run Time in section 04F of the
Menu. This should remain at 12
hours.
Charger Mode: PRO-Verter High-temp Protection
The PRO-Verter is equipped with a function that will temporarily reduce the amount of current that
passes to the batteries should the internal “Transformer Temperature” reach or exceed a preset value
during the charging process. When this is occurring, the LED charge light will blink while charging
continues at a decreased rate. After the transformer cools to a temperature below the preset value,
the LED will stop blinking and remain on constantly and full-capacity charging will resume.