HYD 5-20KTL-3PH
User manual
Copyright ©Shenzhen SOFARSOLAR Co., Ltd
- 62 -
2. Battery Active
2.Battery Active
OK
Automatic activation
Enable
Disable
Mandatory activation
OK
This function provides different ways to activate the battery after battery dormancy.
When the automatic activation switch-disable, when the input and output meet the
conditions for battery activation, the inverter will not automatically activate the
battery, it is necessary to set the mandatory activation LCD to enable the inverter to
activate the battery. When the automatic activation switch-enabling, the inverter
can automatically activate the battery when the input and output meet the
conditions for battery activation. When manual click settings force activation, the
inverter forces the activation of dormant batteries.
3. Anti Reflux
The user can enable
“
Anti Reflux Control
”
to limit the max export power to grid.
Reflux Power set is desired max export power to grid. Refer to 5.6.5 for connection
of the system when using Anti Reflux function.
3.Anti Reflux
OK
1.Anti Reflux Mode
OK
Disable
Anti Reflux
Three phase limit
2.Reflux Power
OK
***KW
4. IV Curve Scan
The user can enable “IV Curve Scan” (MPPT scan) to make inverter to find the
global max power point periodically to deliver max power from a partially shaded
PV array.
The user can input scan period or make inverter to perform a scan right away.
4.IV Curve Scan
OK 1.Scan Control
OK
Enable
Disable
2.Scan Period
OK
***min
3.Force Scan
OK