abnormal occasionally. Inverter will
automatically return to normal operating
status when the electric grid’s back to
normal.
If the alarm occurs frequently, check
whether the grid voltage/frequency is within
the acceptable range. If yes, please check
the AC circuit breaker and AC wiring of the
inverter.
If the grid voltage/frequency is NOT within
the acceptable range and AC wiring is
correct, but the alarm occurs repeatedly,
contact technical support to change the grid
over-voltage, under-voltage,
over-frequency, under-frequency protection
points after obtaining approval from the
local electrical grid operator.
ID007
LvrtLow
LVRT function is faulty
ID008
IslandFault
Island protection error
ID009
GridOVPInstant1
Transient overvoltage
of grid voltage 1
ID010
GridOVPInstant2
Transient overvoltage
of grid voltage 2
ID011
VGridLineFault
Power grid line voltage
error
ID012
Vinvfault
Inverter voltage error
Internal faults of inverter, switch OFF
inverter, wait for 5 minutes, then switch ON
inverter. Check whether the problem is
solved.
If no, please contact technical support.
ID013
RefluxFault
Anti-Reflux function is
faulty
ID017
HwADFaultIGrid
Power grid current
sampling error
ID018
HwADFaultDCI
Wrong sampling of dc
component of grid
current
ID019
FaultVGrid(DC)
Power grid voltage
sampling error (DC)
ID020
FaultVGrid(AC)
Power grid voltage
sampling error (AC)
ID021
GFCIFault(DC)
Leakage current
sampling error(DC)
ID022
GFCIFault(AC)
Leakage current
sampling error(AC)
ID023
HwADFaultDCV
Error in dc component
sampling of load
voltage
ID024
HwADFaultIdc
Dc input current
sampling error
ID029
GFCI Inconsist
Leakage current
consistency error
ID030
Vgrid Inconsist
Grid voltage
consistency error
ID031
DCI Inconsist
DCI consistency error
ID033
Spi Fault(DC)
SPI communication
error (DC)
ID034
Spi Fault(AC)
SPI communication
error (AC)
ID035
SChip_Fault
Chip error (DC)