HYD 5-20KTL-3PH
User manual
Copyright ©Shenzhen SOFARSOLAR Co., Ltd
- 58 -
Testing 81>S2…
↓
Wait
Test 81>S2 OK!
↓
Wait
Testing 81<S1...
↓
Wait
Test 81<S1 OK!
↓
Wait
Testing 81<S2...
↓
Wait
Test 81<S2 OK!
↓
Press “Ok”
Auto Test OK!
↓
Press “Down”
59.S1 threshold 253V 900ms
↓
Press “Down”
59.S1: 228V 902ms
↓
Press “Down”
59.S2 threshold 264.5V
200ms
↓
Press “Down”
59.S2: 229V 204ms
↓
Press “Down”
27.S1 threshold 195.5V
1500ms
↓
Press “Down”
27.S1: 228V 1508ms
↓
Press “Down”
27.S2 threshold 34.5V 200ms
↓
Press “Down”
27.S2: 227V 205ms
↓
Press “Down”
81>.S1 threshold 50.5Hz
100ms
↓
Press “Down”
81>.S1 49.9Hz 103ms
↓
Press “Down”
81>.S2 threshold 51.5Hz
100ms
↓
Press “Down”
81>.S2 49.9Hz 107ms
↓
Press “Down”
81<.S1 threshold 49.5Hz
100ms
↓
Press “Down”
81<.S1 50.0Hz 105ms