SOFAR 3K~6KTLM-G3
User manual
Copyright © Shenzhen SOFAR SOLAR Co., Ltd
- 55 -
protection
where there is no direct sunlight.
Please ensure that the inverter is
installed in a cool/well ventilated
place.
Ensure the inverter is installed
vertically and the ambient temperature
is below the
inverter temperature
limit.
ID050
TempFault_Heat
Sink1
Radiator 1 temperature
protection
ID051
TempFault_Heat
Sink2
Radiator 2 temperature
protection
ID052
TempFault_Heat
Sin3
Radiator 3 temperature
protection
ID053
TempFault_Heat
Sink4
Radiator 4 temperature
protection
ID054
TempFault_Heat
Sin5
Radiator 5 temperature
protection
ID055
TempFault_Heat
Sin6
Radiator 6 temperature
protection
ID057
TempFault_Env1
Ambient temperature 1
protection
ID058
TempFault_Env2
Ambient temperature 2
protection
ID059
TempFault_Inv1
Module 1 temperature
protection
ID060
TempFault_Inv2
Module 2 temperature
protection
ID061
TempFault_Inv3
Module 3 temperature
protection
ID065
VbusRmsUnbala
nce
Unbalanced bus voltage
RMS
Internal faults of inverter, switch OFF
inverter, wait for 5 minutes, then
switch ON inverter. Check whether the
problem is solved.
If no, please contact technical support.
ID066
VbusInstantUnba
lance
The transient value of
bus
voltage
is
unbalanced
ID067
BusUVP
Busbar
undervoltage
during grid-connection
ID068
BusZVP
Bus voltage low
ID069
PVOVP
PV over-voltage
Check whether the PV series voltage
(Voc) is higher than the maximum
input voltage of the inverter. If so,
adjust the number of PV modules in
series and reduce the PV series voltage
to fit the input voltage range of the
inverter. After correction, the inverter
will automatically return to its normal
state.
ID070
BatOVP
Battery over-voltage
Check whether the battery overvoltage
setting is inconsistent with the battery
specification.