be wired by the customer. The appearance of
AC connector
is shown in figure
4-10.
Figure 4-10 AC connector
Step 1
Select appropriate cables according to Table 4-2, Remove the insulation
layer of the AC output cable using a wire stripper according to the figure shown
below: A:15-25mm B:6~8mm
Step 2
Disassemble the AC connector according to the figure shown below:
insert the AC output cable (with its insulation layer stripped according to step 1)
through the waterproof locking cable gland.
Step 3
Connect AC output cable as per the following requirements:
Connect the yellow-green wire to the hole labeled "PE", fasten the wire using an
Cross screwdriver;
Connect the brown wire to the hole labeled "L", fasten the wire using an Cross
screwdriver;
Connect the blue wire to the hole labeled "N", fasten the wire using an Cross
screwdriver.
Step 4
Insert the AC connector and hear "click", then tighten the waterproof
nut at the instantaneous value, as shown in the figure below, to ensure that the
cable is firmly connected.