SOFAR 3K~6KTLM-G3
User manual
Copyright © Shenzhen SOFAR SOLAR Co., Ltd
- 24 -
Follow-up Procedure
To remove the positive and negative connectors from the inverter, insert a
removal wrench into the bayonet and press the wrench with an appropriate
strength, as shown in Figure 4-7.
Before removing the positive and negative connectors, ensure that
the DC SWITCH is OFF.
Caution
Figure 4-7 Removing a DC input connector
4.4. Connecting AC Output Power Cables
Connect the SOFAR 3K~6KTLM-G3 to the AC power distribution frame or
power grid using AC output power cables.
It is not allowed for several inverters to use the same circuit breaker.
It is not allowed to connect loads between inverter and circuit breaker.
AC breaker used as disconnect device,and the disconnect device shall
remain readily operable.
Caution
Context
SOFARSOLAR has already integrated RCMU (residual current monitoring unit)
inside inverter, If an external RCD is required, a type-A RCD with rated residual
current of 100mA or higher is suggested. Please check with the local regulation
for the sizing of rated residual current.
All the AC output cables used for the inverters are outdoor three-core cables. To
facilitate the installation, use flexible cables. Table 4-2 lists the recommended
specifications for the cables.