15

EN

AP9. PRESSURE CONTROL MODE – VSD1-P, VSD3-P

This  section  explains  how  to  configure  the

PRESSURE  CONTROL

control  mode.  This  mode  allows  the  drive  to

regulate the speed of the ventilator depending on the overpressure between to places.

9.1 PROGRAMMING

Use the next table to change to, or modify the pressure control mode.

Table “PRESSURE CONTROL”

1.

In order to make the regulation more dynamic, change the



o



parameters. Increase



until the output

is fast enough. The increase



as much as possible and stop before the system oscillates.

2.

See section 9.2 for the setpoint configuration.

9.2 PRESSURE SETPOINT ADJUSTMENT

The  pressure  setpoint  is  adjusted  in  the



parameter. The  value  read  by  the  drive is  shown  in  the  only-read

parameter



, if the probe has a display the user will be able to see the value directly. This parameters are shown

as percentages and will translate to a different value of Pa, subject to the chosen scale of the probe.

Scale

Pressure in Pa

for every 10% of the Setpoint

Scale

Pressure in Pa

for every 10% of the Setpoint

±100 Pa

20 Pa

*

0-1000 Pa

100 Pa

0-100 Pa

10 Pa

0-1500 Pa

150 Pa

0-250 Pa

25 Pa

0-2000 Pa

200 Pa

0-500 Pa

50 Pa

0-2500 Pa

250 Pa

(*)

Increase for every 10%, subtract 100 Pa to obtain the real value

Parameter

Description

Adjustment

Units



Maximum Frequency

50.0

Hz



Minimum Frequency

20.0

Hz



Acceleration Ramp Time

10

s



Deceleration Ramp Time

10

s



Motor Rated Current

x.x

A



Primary Command Source

5



Extended Menu Access code

101



Analog Input 1 Signal format

U 0-10

V



PI Controller Proportional Gain

0.2

%



PI Controller Integral Time

3.0

s



PI Controller Operating Mode

0



PI Reference (Setpoint) Source Select

0



PI Digital Setpoint

xx.x

%



PI Feedback Source Select

1

ATTENTION:

If there’s a power loss while the ventilator is working and the RUN switch is closed,

the drive will enter the stop stage and show



on the display. Once the power is restored, if

the RUN switch is still closed, the drive will maintain the stop status. In order to start again, the

RUN switch must be opened and closed again. This operation can be modified setting the



mode in the



parameter.

Summary of Contents for VSD/A

Page 1: ...Doc Num 0000003909 2016 05 06 VSD A ES EN Wiring and Configuration Manual Convertidor de Frecuencia Variable Frequency Drive Conversor de frequ ncia IP20 IP66 NEMA 4X 0 37 22Kw 0 5 30HP 110 480V www s...

Page 2: ......

Page 3: ...Fig 6 Fig 9 VSD A...

Page 4: ...ss o diferencial SI PRESI N TPDA JP5 JP1 TERMINAL 1 TERMINAL 2 ES Escala de medida sonda Tipo de salida anal gica Salida anal gica y bus Alimentaci n sonda EN Measuring probe scale Analog output type...

Page 5: ...jumper 5 instalado Elimine el jumper al terminar EN The measurement units can be changed only with the jumper 5 installed Remove the jumper at the end PT As unidades de medida apenas podem ser alterad...

Page 6: ...P5 FIRE MODE WITH NC ACTIVATION SIGNAL Analog speed potentiometer 8 5 1 PROGRAMMING 8 5 2 WIRING 8 5 3 FIRE MODE with Analog Speed OPERATION MODE 8 AP6 FIRE MODE CO WITH NO OR NC ACTIVATION SIGNAL Pre...

Page 7: ...gations recommendations that are instructed in the VSD A User Guide This is an instructive guide about the applications and does not replace the complete guide it s an addition It is the user responsi...

Page 8: ...dge between terminals 1 2 is closed The display will show 2 Press the START key The display will show and the drive will increase the speed until it reaches the minimum speed programmed in the paramet...

Page 9: ...iometer is in the lower speed position the drive will stay at minimum velocity programmed in the P 02 parameter 2 The speed can be increased or decreased with the potentiometer 3 The drive will increa...

Page 10: ...will increase gradually with the acceleration ramp previously programmed until the key is no longer pressed The acceleration ramp is adjusted in the parameter check before the start 4 Press to decrea...

Page 11: ...changes to closed position and the drive is receiving the start signal it can be the a contact of the fire mode the drive will work at a preset speed with all the protections disabled See Fig 4 MODO F...

Page 12: ...1 4 When the two signals aren t active the drive will start to decelerate and stop showing in the display 5 The Fire signal disables the protection features so the drive will maintain continuous opera...

Page 13: ...Once the FIRE MODE with NC contact control mode is selected that is after introducing the parameters of the fire mode table section 5 1 wire the drive as seen in the picture See Fig 6 The Fire signal...

Page 14: ...he display and will wait until it receives an order CO or FIRE MODO FUEGO CO with NC activation signal If the fire signal is active that is when the activation signal goes from normally closed to norm...

Page 15: ...nal triggers the Fire mode as well as the start signal Run If necessary use a two contact Normally Open relay 2 Verify that the CO mode signal triggers the CO mode as well as the start signal Run If n...

Page 16: ...change to or modify the CO2 mode Table CO2 1 In order to make the regulation more dynamic change the o parameters Increase until the output is fast enough The increase as much as possible and stop bef...

Page 17: ...e to find this jumpers See Fig 10 7 5 CO2 OPERATION MODE 1 Close the RUN switch connected between the terminals 1 2 to start the drive The display will show and the drive will increase the speed until...

Page 18: ...URATION Is recommended to adjust the output signal to 0 10V and the sensor SI TEMP IND measuring scale This adjustment by means of the jumpers JP1 and JP2 respectively Remove the cover of the probe to...

Page 19: ...int configured in 2 If the parameter is set at 0 and the temperature exceeds the set point value configured in the inverter VSD A will decrease the speed in order to keep it on the configured value On...

Page 20: ...ressure in Pa for every 10 of the Setpoint Scale Pressure in Pa for every 10 of the Setpoint 100 Pa 20 Pa 0 1000 Pa 100 Pa 0 100 Pa 10 Pa 0 1500 Pa 150 Pa 0 250 Pa 25 Pa 0 2000 Pa 200 Pa 0 500 Pa 50 P...

Page 21: ...et up For example the user should connect the jumper 2 and open the jumpers 1 3 to adjust the probe between 0 and 250 Pa on the pressure transducer SI PRESSURE TPDA See Fig 12 and 13 9 5 PRESSURE CONT...

Reviews: