background image

12

EN

7.2 SETPOINT ADJUSMENT OF THE CO2 CONCENTRATION

The setpoint is adjusted in the



parameter. This parameter is shown as a percentage and will translate to a different

value of CO

2

concentration in ppm, subject to the chosen scale of the probe.

Scale

CO

2

concentration in ppm

per every 10% of the Setpoint

450-1850 ppm

140 ppm

*

0-1000 ppm

100 ppm

0-1500 ppm

150 ppm

0-2000 ppm

200 ppm

(*) Increase for every 10%, add 450 ppm to obtain the real value

7.3 WIRING

Before the start of the programming, wire the L1-L2-L3 input phases when using three phase equipment and wire the

L1-L2/N input phases when using single phase equipment.

Once the

“CO2”

control mode is selected, that is after introducing the parameters of the CO

2

mode table (section 7.1),

wire the drive as seen in the picture.

(See Fig. 9.)

.

The RUN signal must be connected between the terminals 1 & 2, and the switch is always closed, the drive will start

automatically when given power. If the user wants to stop the operation with a selector, timer, etc.… Set up a free

potential contact in series between the terminals 1 & 2.

7.4 PROBE SI-CO2 IND CONFIGURATION

It’s advised to adjust the scale of the probe SI-CO2 IND between 0 and 1000 ppm and the output signal 0-10 V. This

adjustment by means of the jumpers JP5 and JP1 respectively. Remove the cover of the probe to find this jumpers. (

See

Fig. 10)

7.5 “CO2” OPERATION MODE

1.

Close the RUN switch connected between the terminals 1 & 2 to start the drive. The display will show



and

the  drive  will  increase  the  speed  until  reaching  the  objective  speed.  This  speed  is  subjected  to  the  CO2
concentration level detected by the probe and the setpoint adjusted in



.

2.

If the CO2 level goes over the setpoint adjusted in



the drive will increase the speed in order to decrease the

CO2 level below the setpoint.

3.

If the CO2 level goes below the setpoint adjusted in



the drive will decrease the speed in order to keep the

CO2 level below the setpoint.

4.

If the user wants the drive to be always working, short-circuit the terminals 1 & 2 with a copper wire.

5.

If the



parameter has a value >0.0s, the drive will disconnect automatically when the CO2 level goes below

the setpoint for a certain amount of time, adjusted in this parameter. If this feature is active and the CO2 level goes
below the setpoint for an amount of time higher than the one set in



, the drive will stop even when the RUN

switch is closed and won’t start again until the CO2 level goes over the setpoint.

6.

While the drive is ON, the user can see the motor consume pressing the Navigator key

>2 seconds.

VSD*/A Wirings

Terminal VSD*/A

Description

L/N+PE

Single phase input, only for VSD1/A

L1/L2/L3+PE

Three phase input, only for VSD3/A

U/V/W+PE

Three phase motor output

1

+24 VDC (100 mA)

2

Run signal

6

Analog input 1

7

0 V analog input

9

0 V

10

Output relay

11

‘Drive OK’ = Closed

Summary of Contents for VSD/A

Page 1: ...Doc Num 0000003909 2016 05 06 VSD A ES EN Wiring and Configuration Manual Convertidor de Frecuencia Variable Frequency Drive Conversor de frequ ncia IP20 IP66 NEMA 4X 0 37 22Kw 0 5 30HP 110 480V www s...

Page 2: ......

Page 3: ...Fig 6 Fig 9 VSD A...

Page 4: ...ss o diferencial SI PRESI N TPDA JP5 JP1 TERMINAL 1 TERMINAL 2 ES Escala de medida sonda Tipo de salida anal gica Salida anal gica y bus Alimentaci n sonda EN Measuring probe scale Analog output type...

Page 5: ...jumper 5 instalado Elimine el jumper al terminar EN The measurement units can be changed only with the jumper 5 installed Remove the jumper at the end PT As unidades de medida apenas podem ser alterad...

Page 6: ...P5 FIRE MODE WITH NC ACTIVATION SIGNAL Analog speed potentiometer 8 5 1 PROGRAMMING 8 5 2 WIRING 8 5 3 FIRE MODE with Analog Speed OPERATION MODE 8 AP6 FIRE MODE CO WITH NO OR NC ACTIVATION SIGNAL Pre...

Page 7: ...gations recommendations that are instructed in the VSD A User Guide This is an instructive guide about the applications and does not replace the complete guide it s an addition It is the user responsi...

Page 8: ...dge between terminals 1 2 is closed The display will show 2 Press the START key The display will show and the drive will increase the speed until it reaches the minimum speed programmed in the paramet...

Page 9: ...iometer is in the lower speed position the drive will stay at minimum velocity programmed in the P 02 parameter 2 The speed can be increased or decreased with the potentiometer 3 The drive will increa...

Page 10: ...will increase gradually with the acceleration ramp previously programmed until the key is no longer pressed The acceleration ramp is adjusted in the parameter check before the start 4 Press to decrea...

Page 11: ...changes to closed position and the drive is receiving the start signal it can be the a contact of the fire mode the drive will work at a preset speed with all the protections disabled See Fig 4 MODO F...

Page 12: ...1 4 When the two signals aren t active the drive will start to decelerate and stop showing in the display 5 The Fire signal disables the protection features so the drive will maintain continuous opera...

Page 13: ...Once the FIRE MODE with NC contact control mode is selected that is after introducing the parameters of the fire mode table section 5 1 wire the drive as seen in the picture See Fig 6 The Fire signal...

Page 14: ...he display and will wait until it receives an order CO or FIRE MODO FUEGO CO with NC activation signal If the fire signal is active that is when the activation signal goes from normally closed to norm...

Page 15: ...nal triggers the Fire mode as well as the start signal Run If necessary use a two contact Normally Open relay 2 Verify that the CO mode signal triggers the CO mode as well as the start signal Run If n...

Page 16: ...change to or modify the CO2 mode Table CO2 1 In order to make the regulation more dynamic change the o parameters Increase until the output is fast enough The increase as much as possible and stop bef...

Page 17: ...e to find this jumpers See Fig 10 7 5 CO2 OPERATION MODE 1 Close the RUN switch connected between the terminals 1 2 to start the drive The display will show and the drive will increase the speed until...

Page 18: ...URATION Is recommended to adjust the output signal to 0 10V and the sensor SI TEMP IND measuring scale This adjustment by means of the jumpers JP1 and JP2 respectively Remove the cover of the probe to...

Page 19: ...int configured in 2 If the parameter is set at 0 and the temperature exceeds the set point value configured in the inverter VSD A will decrease the speed in order to keep it on the configured value On...

Page 20: ...ressure in Pa for every 10 of the Setpoint Scale Pressure in Pa for every 10 of the Setpoint 100 Pa 20 Pa 0 1000 Pa 100 Pa 0 100 Pa 10 Pa 0 1500 Pa 150 Pa 0 250 Pa 25 Pa 0 2000 Pa 200 Pa 0 500 Pa 50 P...

Page 21: ...et up For example the user should connect the jumper 2 and open the jumpers 1 3 to adjust the probe between 0 and 250 Pa on the pressure transducer SI PRESSURE TPDA See Fig 12 and 13 9 5 PRESSURE CONT...

Reviews: