4
EN
AP2. EXTERNAL KIT MODE –
Manipulate with the MTP 010 remote control
This section explains how to proceed with the configuration of the
“EXTERNAL REMOTE CONTROL KIT –
MTP010”
control mode. This simple control mode allows to start the drive and adjust the speed from the exterior remote
control kit
MTP010
.
2.1 PROGRAMMING
Use the next table to change the mode to the external kit mode.
Table “EXTERNAL REMOTE CONTROL KIT”
2.2 WIRING
Before the start of the programming, wire the L1-L2-L3 input phases when using three phase equipment and wire the
L1-L2/N input phases when using single phase equipment.
Once the
“EXTERNAL REMOTE CONTROL KIT”
control mode is selected, that is after introducing the parameters of
the external remote control kit table (section 2.1), wire the remote control as seen in the picture.
(See Fig. 3)
.
2.3 “EXTERNAL REMOTE CONTROL KIT” OPERATION MODE
1. To start the drive, close the built-in switch of the remote control (starting switch ON). The display will stop showing
and the drive will accelerate towards the speed adjusted by the potentiometer. If the potentiometer is in the
lower speed position, the drive will stay at minimum velocity, programmed in the
P-02
parameter.
2. The speed can be increased or decreased with the potentiometer.
3. The drive will increase gradually, with the acceleration ramp programmed in
P-03.
Check before the start.
4. The drive will decrease gradually, with the deceleration ramp programmed in
P-04.
Check before the start.
5. When the starting switch is OFF, the drive will start to decelerate and stop, showing
in the display. The drive
is disabled
6. While the drive is enabled, we can visualize the consumption of the motor by pressing the navigator key
>2
seconds.
Parameter
Description
Adjustment
Units
Maximum Frequency
50.0
Hz
Minimum Frequency
20.0
Hz
Acceleration Ramp Time
20
s
Deceleration Ramp Time
20
s
Motor Rated Current
x.x
A
Primary Command Source
0
ATTENTION:
If there’s a loss of the power supply while the ventilator is working with the starting
switch closed, the drive will be disabled with the display showing
. Once the power supply
is restored, the drive will be disabled even with the starting switch ON. In order to start the drive
again, the switch must be changed to the OFF position and then changed again to the ON
position. See
parameter to modify the configuration and change it to
.
Summary of Contents for VSD/A