MASTERYS BC+ 60-80 kVA - Ref.: IOMMASBCXX0F-EN 00
3. ENVIRONMENTAL REQUIREMENTS AND HANDLING
NOTE!
Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
3.1 ENVIRONMENTAL REQUIREMENTS
The room must be:
• of a suitable size
• free from conductive, inflammable and corrosive items;
• not exposed directly to sunlight.
The floor must support the weight of the unit and guarantee its stability.The unit is designed for indoor installation
only.
ROOM POSITIONING
For information regarding ambient temperature, dimensions and weights refer to the 'Technical specifications' chap-
ter.
UPS OR OTHER
CABINET
UPS
Free area:
ł
80cm
Free area:
ł
20cm
Free area:
ł
150cm
UPS OR OTHER
CABINET
FRONT