MASTERYS BC+ 60-80 kVA - Ref.: IOMMASBCXX0F-EN 00
11.10 KIT FOR COMMON MAINS
WARNING!
Cabling errors with inversion between phase and neutral conductors may cause permanent
damage to the equipment.
Details
L3
L2
L1
N
N
L3
L2
L1
N
L3
L2
L1
Aux mains
Input
Input mains
11.11 KIT FOR RECTIFIER NEUTRAL CREATION
For three wire input mains (without neutral) a neutral kit is available as an option. The neutral kit does not change the
type of grounding system and it does not create galvanic insulation.
An input mains neutral bar is not available.
The input mains and auxiliary mains must be separate.
The auxiliary mains must always have a neutral wire.
The auxiliary mains neutral wire must be galvanically isolated from the PE.