32
EN
MASTERYS BC+ 60-80 kVA - Ref.: IOMMASBCXX0F-EN 00
Function mode
Description
The UPS is in maintenance mode
Output breaker / output relays open
Eco mode schedule enabled
An eco mode command has been carried out
A remote stand-by command has been carried out
The energy-saver mode has been enabled
<NOTHING DISPLAYED>
Normal mode
Mimic panel
7
6
5
4
3
2
1
SEGMENT
DESCRIPTION
1
INPUT MAINS
2
RECTIFIER ON
3
INVERTER INPUT OR BATTERY
OUTPUT
4
INVERTER OUTPUT
5
UNIT OUTPUT
6
OUTPUT FROM STATIC SWITCH
7
BYPASS INPUT
NOTE!
When in converter mode, 6 and 7 are not shown.
Bar styles identify the energy flow: