MASTERYS BC+ 60-80 kVA - Ref.: IOMMASBCXX0F-EN 00
9. OPERATING PROCEDURES
NOTE: before carrying out any operations on the unit read the 'Safety standards' chapter care-
fully.
NOTE: with the stop procedure the load will be disconnected.
9.1 SWITCHING ON
• Connect the mains and auxiliary mains to the UPS.
• Switch
ON
input switch
Q1
.
• Wait until display switch on.
• Enter MAIN MENU > CONTROLS > PROCEDURE.
• Select START PROCEDURE and press
ENTER
.
• Carry out the operations indicated on the display.
9.2 SWITCHING OFF
This operation interrupts the power supply to the load. The UPS and the battery charger will be shut down.
• Enter MAIN MENU > CONTROLS > PROCEDURE.
• Select STOP PROCEDURE and press
ENTER
.
• Wait approx. 2 minutes for the UPS shutdown.
NOTE: the controlled shutdown of each server connected to the LAN can be managed by shut-
down software.
• Carry out the operations indicated on the display.
9.3 BYPASS OPERATIONS
SWITCHING ONTO MAINTENANCE BYPASS
This operation creates a direct connection between the UPS input and output, excluding the equipment control part.
This operation is performed in the event of:
- standard maintenance.
- serious failure has occurred.
WARNING! LOAD POWERED BY AUX MAINS: your load is exposed to mains disturbances.
• Enter MAIN MENU > CONTROLS > PROCEDURE.
• Select MAINT. BYPASS PROC. and press
ENTER
.
• Carry out the operations indicated on the display.
NOTE!
When an external manual bypass is present:
- carry out the procedure described above;
- put the switch to position 1.
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK