background image

16

NETYS PR RACK 1U

 - Ref.: IOMNETPRXX01-GB  02

9. TROUBLESHOOTING

Alarm or Condition

Possible Cause

Action

 1 beep every 2 seconds.

The UPS is running on battery 
power because the input 
voltage is too high (>149V 
for 120V models; >290V 
for 230V models) or too low 
(<30V).

Correct the input voltage, if possible. The UPS continues 
to operate on battery until the condition is corrected or the 
battery is completely discharged.

If the condition persists, the input voltage in your area may 
differ from the UPS nominal.

1 beep per second.

Power requirements exceed 
UPS capacity (overload is 
greater than 110%) or the 
load is defective.

The UPS will automatically shut down in 3 minutes. Save 
your work immediately and turn off your equipment. Turn 
off the UPS. The alarm cannot be silenced.

Remove some of the equipment from the UPS. You may 
need to obtain a larger capacity UPS.

1 beep per second.

The UPS is on battery, and 
the power requirements 
exceed UPS capacity (over-
load is greater than 110%) or 
the load is defective.

Shutdown is imminent (30 seconds). Save your work and 
turn off your equipment. Turn off and unplug the UPS. The 
alarm cannot be silenced.

Remove some of the equipment from the UPS. Wait at 
least 5 seconds until all LEDs are off and restart the UPS. 
You may need to obtain a larger capacity UPS.

Continuous beep.

Battery test failed.

Check the battery connections and be sure the battery is 
fully charged.

If the 

 indicator still flashes, see "UPS Maintenance" on 

page 39 to replace the battery. Call your service represen-
tative if the problem persists.

Continuous beep.

UPS internal temperature is 
too high.

Shutdown is imminent. Save your work and turn off your 
equipment. Turn off and unplug the UPS. The alarm 
cannot be silenced.

Clear vents and remove any heat sources. Ensure the 
airflow around the UPS is not restricted. Wait at least 5 
minutes and restart the UPS. If the condition persists, 
contact your service representative.

Continuous beep.

UPS fan fault.

Save your work and turn off your equipment. Turn off and 
unplug the UPS. Contact your service representative. The 
alarm cannot be silenced.

3 beeps every 10 seconds.

Failed attempt to start the 
UPS on battery.

Plug the UPS into a power outlet for 24 hours to charge 
the battery. After charging the battery, press and hold the  

 button for 3 seconds; then check the indicator. The 

alarm cannot be silenced.

If the 

 indicator still flashes, see "UPS Maintenance" on 

page 39 to replace the battery.

Continuous beep.

The output wave is abnormal 
while the UPS is on battery.

Shutdown is imminent. Save your work and turn off your 
equipment. Turn off and unplug the UPS. Contact your 
service representative. The alarm cannot be silenced.

Continuous beep.

The output voltage is below or 
above the limit while the UPS 
is on battery.

Save your work and turn off your equipment. Turn off and 
unplug the UPS. Contact your service representative. The 
alarm cannot be silenced.

If the equipment is to be left idle for a long period, wait for the batteries to charge fully before switching off. While 
the ups is left idle, make sure that the batteries are recharged for 24 hours at least once every 4 weeks.

Summary of Contents for NETYS PR 1000 Rack 1U

Page 1: ...stallation et d utilisation FR Installation and operating manual GB Manuale di installazione e uso IT MK Installatie en bedieningshandleiding NL Dokumentacja Techniczno Ruchowa PL Manual de instala o...

Page 2: ...y temperature poor ventilation etc tampering or any unauthorised repair work During the warranty period SOCOMEC UPS reserves the right to decide whether the product should be repaired or whether to re...

Page 3: ...ECTION 11 7 MODES OF OPERATION 12 7 1 TURNING THE UPS ON 12 7 2 TURNING THE UPS OFF 12 7 3 STANDBY MODE 12 7 4 INITIATING THE SELF TEST 12 8 ADDITIONAL UPS FEATURES 13 8 1 VOLTAGE CONFIGURATION 13 8 2...

Page 4: ...ose of batteries in a fire the battery may explode CAUTION A battery can present a risk of electric shock and high short circuit current The following precaution should be observed when working on bat...

Page 5: ...ower supply which duly filtered and stabilised on models with AVR and if considered suitable is used to supply consumers In cases of a mains failure or if the mains is considered to be outside limits...

Page 6: ...9 Rack 3 1 2 Adjusting the Rail Depth 3 1 3 Securing the Rear Rail 3 1 4 Securing the Front Rail Mounting Bracket M3x6 Bracket Screws Rear Hold Down Bracket Rear Front Assembly Wing Nuts Assembly Wing...

Page 7: ...LLATION 3 1 5 Securing the UPS in a 19 Rack 3 1 6 Rack Tray and Mounting Bracket for a 23 Cabinet 3 1 7 Securing the UPS in a 23 Rack Mounting Bracket M3x6 Bracket Screws Rack Tray NOTE Rails cannot b...

Page 8: ...GB 02 3 INSTALLATION 3 1 8 Zero U Mounting 3 1 9 Mounting the UPS to a Wall Side of Rack Cabinet within 22 54 22 78 or 56 35 56 95 cm WARNING The UPS MUST be positioned with the front panel at the to...

Page 9: ...ef IOMNETPRXX01 GB 02 ENGLISH Load segment 1 green Service red Overload red Load segment 2 green Battery mode yellow Power ON green ON OFF button Test Alarm reset button 4 FRONT VIEW 4 1 2 Control pan...

Page 10: ...e Slot for optional communication boards Slot for optional communication boards Main input socket IEC 320 Main input socket IEC 320 DIP Switches DIP Switches RS232 serial port RS232 serial port USB Po...

Page 11: ...connector 6 1 3 Reinstall the UPS front panel Verify that the UPS is off and unplugged Remove the UPS front panel figure 6 1 1 Connect the battery connector figure 6 1 2 A small amount of arcing may...

Page 12: ...pment and goes into Battery mode 7 2 TURNING THE UPS OFF To turn off the UPS press and hold the button for two seconds and then unplug the UPS from the power outlet If you do not unplug the UPS it rem...

Page 13: ...FF 230 V 207 V 243 V OFF OFF ON 240 V 216 V 254 V ON ON Default position DIP Switch Settings 8 2 NETWORK TRANSIENT PROTECTOR The Network Transient Protector is located on the rear panel and has jacks...

Page 14: ...gh Java Shutdown Client technology Web SNMP card 9 2 RS232 INTERFACE Communication with the server can take place directly via the RS232 interface In addition to local or networked shutdown it is poss...

Page 15: ...correctly Check the power cord connections The UPS is in Standby mode Press and hold the button until you hear the UPS beep approximately two seconds to supply power to the connected equipment The wal...

Page 16: ...to replace the battery Call your service represen tative if the problem persists Continuous beep UPS internal temperature is too high Shutdown is imminent Save your work and turn off your equipment Tu...

Page 17: ...cuit protected Load connection socket IEC 320 4 10 A Battery Typical back up time 12 minutes Battery recharge Advanced charging for faster recovery Approximately 3 hours to 90 usable capacity at nomin...

Page 18: ......

Page 19: ......

Page 20: ...UNITED KINGDOM Units 7A 9A Lakeside Business Park Broadway Lane South Cerney Cirencester GL7 5XL Tel 44 0 1285 863300 info ups uk socomec com OTHER COUNTRIES Tel 34 935 407 575 info ups europe socome...

Reviews: