13
NETYS PR RACK 1U
- Ref.: IOMNETPRXX01-GB 02
ENGLISH
8.1. VOLTAGE
CONFIGURATION
The DIP switches on the UPS rear panel (see Figure 14) are used to configure the output voltage and input voltage range.
1. The UPS must be completely shutdown. To turn off the UPS, press and hold the button for two seconds and then unplug the
UPS from the power outlet.
2. Set the DIP switches according to the configurations in Table 1.
3. Plug the UPS into a power outlet.
4. Press and hold the button until you hear the UPS beep (approximately two seconds) to turn the UPS on.
8. ADDITIONAL UPS FEATURES
OFF
ON
2
1
8.1-1
DIP Switches
UPS Rear Panel
230 V Models
Output Voltage
Input Voltage Range
DIP Switch 1
DIP Switch 2
220 V
198 V-233 V
ON
OFF
230 V*
207 V-243 V*
OFF
OFF/ON
240 V
216 V-254 V
ON
ON
*Default position
DIP Switch Settings
8.2. NETWORK TRANSIENT PROTECTOR
The Network Transient Protector is located on the rear panel and has jacks labeled IN and OUT. This feature accommodates a
single RJ-45 (10BaseT) network connector.
Low voltage models can also accommodate an RJ-11 telephone connector that provides protection for modems, fax machines,
or other telecommunications equipment. As with most modem equipment, it is not advisable to use this jack in digital PBX (Private
Branch Exchange) environments.
NOTE
DO NOT connect any telephone or fax/modem equipment to the 230 V models; only network protection is available
for 230 V models.
1. Connect the input connector of the equipment you are
protecting to the jack labeled IN.
2. Connect the network or telephone cable (low voltage models
only) to the jack labeled OUT.
8.2-1
Network Transient Protector
In
Out