Connection to the mains power supply and to the load(s) must be made using cables of suitable cross section, in accordance with
current standards.
If not already provided, install a PDU panel allowing isolation of the mains supply upstream of the UPS. The panel must be equipped
with an automatic switch rated high enough to handle the current draw on full load, and with a residual current device.
If requested, the UPS can also be switched off utilizing a remote external
shutdown
contact.
The command is acknowledged when the contact is made and held for 3 seconds (default),
whereas the external contact must be made between the
common
and
input
pins.
The external contact MUST be dedicated and voltage-free, so as not to cause
permanent damage to the UPS.
4. CONNECTIONS
1100 VA
3000 VA
1700 VA
2200 VA
LOAD 1
LOAD 2
IN
OUT
BREAKER
INPUT
INPUT
RS232
EPO
SURGE PROTECT
40A
24V
COM. SLOT
IN
OUT
LOAD 1
LOAD 2
RS232
BREAKER
INPUT
EPO
SURGE PROTECT
LOAD 3
INPUT
40A
72V
COM. SLOT
IN
OUT
LOAD 1
LOAD 2
RS232
BREAKER
INPUT
EPO
SURGE PROTECT
LOAD 3
INPUT
40A
48V
COM. SLOT
OUT 230 V~
3 x IEC320
OUT 230 V~
3 x IEC320
OUT 230 V~
3 x IEC320
OUT 230 V~
3 x IEC320
OUT 230 V~
3 x IEC320
OUT 230 V~
3 x IEC320
IN 230 V~ Use the power
cable provided.
IN 230 V~ Use the power
cable provided.
IN 230 V~ Use the power
cable provided.
1 2 3 4 5 6
4-1
050
DR
WNETR
T-XX
051
DR
WNETR
T-XX
037
DR
WNETR
T-XX
062
DR
WNETR
T-XX