1. SAFETY STANDARDS

1.1 Important

This manual should be kept carefully in a safe place near the UPS, so that it can be consulted by the operator at any time for any 
information that may be needed regarding correct use of the unit. Read the manual carefully before connecting the unit to the a.c. 
mains supply and to the downstream appliances. Before the UPS NETYS RT is put into commission, the user must be perfectly 
familiar with its operation, with the position of all the controls and with the technical and functional characteristics of the unit, so as 
to ensure there will be no risk to any persons or to the appliance itself. 

• 

Before being started up, the unit must be equipotentially bonded, in accordance with current safety regulations. 

The earth 

wire of the UPS must then be connected to an efficient earth system.

• 

If the earth connection is not made, the appliances connected to the UPS will not be equipotentially bonded.

 In this situation, 

the manufacturer declines all liability for any damage or accidents that could derive from failure to observe the requirements.

 Should a power outage occur (UPS in stand-alone mode), do not disconnect the power cord from the mains, as this will 

break the earth connection to bonded appliances.

• 

All subsequent maintenance operations must be entrusted only to authorized service engineers.  

The UPS generates high 

internal voltages that could be hazardous for a maintenance operative not in possession of the appropriate skills and training for 
this type of work.

 If a hazard situation should arise at any moment when the UPS is in use, 

isolate the unit from the power supply (by operating 

a switch at the upstream PDU if possible) and switch the appliance off completely by running the shutdown procedure.

 The UPS houses a source of electrical energy, namely its batteries. The output of the UPS may be under power even 

when the appliance is not connected to the a.c. mains supply.

• 

Never force, break or attempt to open the batteries. These batteries are sealed, maintenance-free components contai-
ning substances that are harmful to health and a source of environmental pollution. If liquid can be seen leaking from the 
battery, or a white powdery residue is noticeable, do not switch the UPS on.

• 

Avoid exposing the UPS to contact with water or any liquids generally.  Do not insert foreign objects into the cabinet.

 If the appliance is to be scrapped, 

it must be entrusted exclusively to a specialist waste disposal company. These companies 

will split up and dispose of the various components in accordance with statutory regulations in the country of purchase.

• Since the power cord of the UPS functions as an isolating device, ensure ready access to the mains power socket where the UPS 

is connected, and/or to the rear panel of the UPS, so the unit can be easily unplugged. 

• The UPS generates a 

leakage current

 of approximately 3 mA. To guarantee the maximum leakage current of 3.5 mA, make certain 

that the leakage current generated by the load is no greater than 0.5 mA. Should the leakage current from the load exceed this 
limit, instruct a skilled engineer to install an industrial type connection (to IEC 309 standard) between the UPS and the a.c. mains 
supply, sized to handle a current compatible with the rating of the appliance. 

• Use the UPS in accordance with the technical specifications indicated in this manual (chapter 11).
• To meet the operating requirements for the Emergency Switch Device (ESD), a specific RJ11 input with remote ESD/EPO function 

is available.

• In the event that the equipment has no automatic backfeed protection contactor device, make certain that:

- the user/installer attaches warning labels to all mains isolating switches located remotely from the area where the UPS is sited, in 

order to inform service personnel that the circuit is connected to a UPS.

- an external isolating device is installed, as indicated in figure 1-1.

  

The product you have selected, given the specified conditions of use, capacity and performance limits, is designed exclusively for 
commercial and industrial service. The use of the product in “critical applications” could require compliance with statutory regula-
tions and standards, or with specific local bylaws, or adaptation to SOCOMEC UPS recommendations. For this type of use, in any 
event, it is advisable to contact SOCOMEC UPS beforehand for confirmation regarding the capacity of products to meet required 
levels of safety, performance and reliability. The expression “critical applications” covers, in particular, life support systems, medical 
applications, commercial transport, nuclear facilities or any other systems where failure of the product might on occasion cause 
serious damage to persons or property.

WARNING!
This is a product for commercial and industrial application in the second environment – installation restrictions or 
additional measures may be needed to prevent disturbances.

Summary of Contents for netis rt

Page 1: ...1 1 1 7 2 2 3 kVA Installation and operating manual GB 004 DRWNETRT XX...

Page 2: ...esult in a reduction of the original warranty period The warranty on the product does not cover damage occasioned by thoughtlessness improper use wrong input power explosions excessive humidity temper...

Page 3: ...NNECTIONS 13 5 CONNECTION OF BATTERY EXTENSION 14 5 1 Safety warnings 14 5 2 Connection of battery extension 14 6 MIMIC PANEL 16 7 OPERATING MODES 17 7 1 Battery recharge 17 7 2 Switching the Netys RT...

Page 4: ...oreign objects into the cabinet If the appliance is to be scrapped it must be entrusted exclusively to a specialist waste disposal company These companies will split up and dispose of the various comp...

Page 5: ...on the inside and outside of the equipment should be respected DANGER HIGH VOLTAGE BLACK YELLOW GROUND TERMINAL READ THE USER MANUAL BEFORE USING THE UNIT 085 DRWNETRT XX 1 1 Legend B Contactor solen...

Page 6: ...k that the operating voltage and frequency settings are correct for the mains power supply at the installation site Details for the UPS will be found on the data plate affixed to the rear panel When m...

Page 7: ...RTXX00 GB 00 ENGLISH 2 INSTALLATION 2 2 Vertical installation 2 2 1 UPS Installation 2 2 2 UPS Installation with 1 battery extension 4 4 2 1 3 026 DRWNETRT XX 031 DRWNETRT XX 035 DRWNETRT XX 059 DRWNE...

Page 8: ...8 1 1 3 kVA Ref IOMNETRTXX00 GB 00 2 2 3 UPS Installation with multiple battery extensions 2 INSTALLATION 4 2 1 3 036 DRWNETRT XX 033 DRWNETRT XX 059 DRWNETRT XX 028 DRWNETRT XX...

Page 9: ...3 kVA Ref IOMNETRTXX00 GB 00 ENGLISH 2 INSTALLATION 2 3 Horizontal installation on rack 2 3 1 Rotation of mimic pannel 038 DRWNETRT XX 043 DRWNETRT XX 042 DRWNETRT XX 041 DRWNETRT XX 039 DRWNETRT XX...

Page 10: ...10 1 1 3 kVA Ref IOMNETRTXX00 GB 00 2 3 2 Fitting rack brackets 2 INSTALLATION 044 DRWNETRT XX 046 DRWNETRT XX 1 2 3 045 DRWNETRT XX...

Page 11: ...ack 1 Adapt the length of the tracks to fit the rack 2 Secure the wing nuts 3 Fix the track to the rack 4 Slot in the UPS and tighten the screws 2 INSTALLATION MAX 100 kg MAX 100 kg MAX 100 kg MAX 100...

Page 12: ...2200 VA G G G F F F E E E D D D B B B C C H H H L L L L M P L N N I I I A A A L O N Legend A Mains input socket IEC 320 B Fan C Output socket full power D Telephone socket input E Telephone socket ou...

Page 13: ...lt whereas the external contact must be made between the common and input pins The external contact MUST be dedicated and voltage free so as not to cause permanent damage to the UPS 4 CONNECTIONS 1100...

Page 14: ...rous to touch any part of the battery storage unit 5 2 Connection of battery extension WARNING Before commencing any operation make certain that the voltages of the UPS battery and of the battery exte...

Page 15: ...ECT 40A 24V COM SLOT IN OUT LOAD 1 LOAD 2 RS232 BREAKER INPUT EPO SURGE PROTECT LOAD 3 INPUT 40A 48V COM SLOT 1100 VA 1700 VA 2200 VA 3000 VA IN OUT LOAD 1 LOAD 2 RS232 BREAKER INPUT EPO SURGE PROTECT...

Page 16: ...Normal operation inverter in line D Red symbol lit Fault E ON TEST and buzzer override button F LED bar Depending on the situation this indi cates either the charge level figure 7 1 1 or the capacity...

Page 17: ...ould occur the duration of the backup will be shorter 7 OPERATING MODES 3 sec 3 sec 7 1 1 7 2 1 1 7 2 2 1 7 2 1 2 7 2 2 2 Normal operation 7 2 1 3 Normal operation 7 2 Switching the Netys RT ON and OF...

Page 18: ...tton to activate deactivate Battery mode the buzzer 7 OPERATING MODES UPS is off but battery remains on charge Shut down all loads one at a time Switch off mains power to shut down completely 10 sec 7...

Page 19: ...or 1 second to exit the procedure 7 3 1 Standby mode 7 3 3 230 Vac mode 230 Vac mode 240 Vac mode 200 Vac mode 1 208 Vac mode 220 Vac mode 7 3 2 7 3 4 7 3 5 006 DRWNETRT XX 136 DRWNETRT XX 136 DRWNETR...

Page 20: ...1 By pass mode 8 7 Overtemperature 8 10 Inverter undervoltage 8 13 DC BUS line overvoltage 8 4 Battery needs replacing 8 2 Overload 8 8 Battery charge failure 8 11 Inverter overvoltage 8 14 High AC i...

Page 21: ...without the need to install any additional software Once connected recognition of the UPS occurs in the same way as for any other peripheral and the operating parameters can be managed by way of the...

Page 22: ...t Tx Rx GND C SW1 SW2 GND R R1 General alarm R2 No mains R3 Battery low R4 On by pass R5 Overload R6 Overtemperature 9 5 1 1 9 5 1 3 9 5 1 2 SW1 SW2 relay contact OFF OFF NO ON OFF NC GND R Relay grou...

Page 23: ...99 seconds maximum 3 Press 3 to configure NO or NC operation of each relay Shift SW2 to the ON position to activate the settings If SW2 is returned to the OFF position SW1 can be used to check the NO...

Page 24: ...f 8 hours UPS in overload Disconnect non essential loads Depleted batteries The batteries will degrade quickly if used fequently or in high operating temperatures Should the batter ies have reached th...

Page 25: ...ut output RJ11 or RJ45 Technology On line double conversion VFI SS 111 Batteries Type Maintenance free sealed lead life expectancy 3 5 years Typical backup 7 minutes 7 minutes 7 minutes 8 minutes Comm...

Page 26: ...wowiejska St 21 25 00 665 Warszawa Tel 48 0 22 2345 223 Fax 48 0 22 2345 223 ups poland socomec com PORTUGAL Rua Moinho do Cuco Bloco A Lj Dta Paz 2640 566 MAFRA Tel 351 261 812 599 Fax 351 261 812 57...

Reviews: