background image

24

 1.1-3 kVA - Ref.: IOMNETRTXX00-GB  00

10. MAINTENANCE

WARNING! 
The UPS generates HAZARDOUS INTERNAL VOLTAGES.  All maintenance operations should be carried out by 
AUTHORIZED SERVICE ENGINEERS ONLY. 

• The unit will operate to its maximum capability if kept powered up round the clock (24/7); this ensures that the batteries will always 

be properly charged.

• If the appliance is to remain idle for any length of time, wait until the batteries are fully charged (connection to mains power supply 

for 8 hours continuous) before shutting the UPS down. 

• Recharge the batteries for a duration of 24 hours at least every 4 weeks during the time the unit remains idle.

10.1 Minor troubleshooting

WARNING! 
If problems should persist or reoccur frequently after following the procedures indicated in this section, contact 
the SOCOMEC UPS After Sales Service, providing a full description of the current difficulty

Problem

Possible cause

Solution

"UPS not powered up 
(no alarm, no LEDs 
alight)”

The ON/TEST button has not been pressed.

Press the ON/TEST button to switch the UPS on. 

Shutdown due to flat battery and no mains 
power.

Wait for mains power to be restored

Thermal-magnetic switch on the rear panel 
has been tripped.

Reduce the load connected to the UPS, then reset 
the thermal-magnetic switch.

Faulty UPS

Contact SOCOMEC UPS After Sales Service if the 
solutions indicated above do not solve the problem.

UPS does not guar-
antee the expected 
backup time.

UPS internal batteries not completely 
charged.

Recharge the batteries for a minimum of 8 hours.

UPS in overload. 

Disconnect non-essential loads.

Depleted batteries. 

The batteries will degrade quickly if used fequently, 
or in high operating temperatures. Should the batter-
ies have reached the end of their life cycle, contact 
SOCOMEC UPS After Sales Service.   Batteries must 
be replaced even if the "Replace battery" LED is not lit. 

Battery charge fault or other causes.

Contact SOCOMEC UPS After Sales Service

"Replace battery" LED 
lit.

Batteries flat.

Charge the batteries for a minimum of 8 hours.   If the 

problem persists, contact SOCOMEC UPS After Sales 
Service to have for battery replacement.

Faulty communication 
between PC and UPS.

Wrong transmission speed.

Change the transmission speed and test again.

RS232 connection incorrect.

See "Communication" section of this manual. 
Reconnect the UPS to the COM1/COM2 port of the PC.

USB connection incorrect.

Reconnect the UPS to the USB port of the PC.

UPS functions in 
"Battery Mode" even 
though a.c. mains is 
connected and healthy.

Mains voltage not registering at UPS input.

Check the input voltage connection.

Thermal-magnetic switch on the rear panel 
has been tripped.

Reduce the load connected to the UPS, then reset 
the thermal-magnetic switch.

Input voltage too high, too low or distorted.

Have the mains voltage checked by a qualified electri-
cian.

Overtemperature.

Air intake fans and fan cowl may be 
obstructed.

Select a well ventilated area in which to position the 
UPS, allowing suitable dissipation of heat.

Ambient temperature is higher than 40 °C 
(104 °F).

Position the UPS in a cooler area.

"Fault" LED lit and alarm 
signal generated. 

UPS faulty.

Contact SOCOMEC UPS After Sales Service.

"Overload" LED lit, with 
continuous alarm signal.

Overload.

Disconnect non-essential loads.

Summary of Contents for netis rt

Page 1: ...1 1 1 7 2 2 3 kVA Installation and operating manual GB 004 DRWNETRT XX...

Page 2: ...esult in a reduction of the original warranty period The warranty on the product does not cover damage occasioned by thoughtlessness improper use wrong input power explosions excessive humidity temper...

Page 3: ...NNECTIONS 13 5 CONNECTION OF BATTERY EXTENSION 14 5 1 Safety warnings 14 5 2 Connection of battery extension 14 6 MIMIC PANEL 16 7 OPERATING MODES 17 7 1 Battery recharge 17 7 2 Switching the Netys RT...

Page 4: ...oreign objects into the cabinet If the appliance is to be scrapped it must be entrusted exclusively to a specialist waste disposal company These companies will split up and dispose of the various comp...

Page 5: ...on the inside and outside of the equipment should be respected DANGER HIGH VOLTAGE BLACK YELLOW GROUND TERMINAL READ THE USER MANUAL BEFORE USING THE UNIT 085 DRWNETRT XX 1 1 Legend B Contactor solen...

Page 6: ...k that the operating voltage and frequency settings are correct for the mains power supply at the installation site Details for the UPS will be found on the data plate affixed to the rear panel When m...

Page 7: ...RTXX00 GB 00 ENGLISH 2 INSTALLATION 2 2 Vertical installation 2 2 1 UPS Installation 2 2 2 UPS Installation with 1 battery extension 4 4 2 1 3 026 DRWNETRT XX 031 DRWNETRT XX 035 DRWNETRT XX 059 DRWNE...

Page 8: ...8 1 1 3 kVA Ref IOMNETRTXX00 GB 00 2 2 3 UPS Installation with multiple battery extensions 2 INSTALLATION 4 2 1 3 036 DRWNETRT XX 033 DRWNETRT XX 059 DRWNETRT XX 028 DRWNETRT XX...

Page 9: ...3 kVA Ref IOMNETRTXX00 GB 00 ENGLISH 2 INSTALLATION 2 3 Horizontal installation on rack 2 3 1 Rotation of mimic pannel 038 DRWNETRT XX 043 DRWNETRT XX 042 DRWNETRT XX 041 DRWNETRT XX 039 DRWNETRT XX...

Page 10: ...10 1 1 3 kVA Ref IOMNETRTXX00 GB 00 2 3 2 Fitting rack brackets 2 INSTALLATION 044 DRWNETRT XX 046 DRWNETRT XX 1 2 3 045 DRWNETRT XX...

Page 11: ...ack 1 Adapt the length of the tracks to fit the rack 2 Secure the wing nuts 3 Fix the track to the rack 4 Slot in the UPS and tighten the screws 2 INSTALLATION MAX 100 kg MAX 100 kg MAX 100 kg MAX 100...

Page 12: ...2200 VA G G G F F F E E E D D D B B B C C H H H L L L L M P L N N I I I A A A L O N Legend A Mains input socket IEC 320 B Fan C Output socket full power D Telephone socket input E Telephone socket ou...

Page 13: ...lt whereas the external contact must be made between the common and input pins The external contact MUST be dedicated and voltage free so as not to cause permanent damage to the UPS 4 CONNECTIONS 1100...

Page 14: ...rous to touch any part of the battery storage unit 5 2 Connection of battery extension WARNING Before commencing any operation make certain that the voltages of the UPS battery and of the battery exte...

Page 15: ...ECT 40A 24V COM SLOT IN OUT LOAD 1 LOAD 2 RS232 BREAKER INPUT EPO SURGE PROTECT LOAD 3 INPUT 40A 48V COM SLOT 1100 VA 1700 VA 2200 VA 3000 VA IN OUT LOAD 1 LOAD 2 RS232 BREAKER INPUT EPO SURGE PROTECT...

Page 16: ...Normal operation inverter in line D Red symbol lit Fault E ON TEST and buzzer override button F LED bar Depending on the situation this indi cates either the charge level figure 7 1 1 or the capacity...

Page 17: ...ould occur the duration of the backup will be shorter 7 OPERATING MODES 3 sec 3 sec 7 1 1 7 2 1 1 7 2 2 1 7 2 1 2 7 2 2 2 Normal operation 7 2 1 3 Normal operation 7 2 Switching the Netys RT ON and OF...

Page 18: ...tton to activate deactivate Battery mode the buzzer 7 OPERATING MODES UPS is off but battery remains on charge Shut down all loads one at a time Switch off mains power to shut down completely 10 sec 7...

Page 19: ...or 1 second to exit the procedure 7 3 1 Standby mode 7 3 3 230 Vac mode 230 Vac mode 240 Vac mode 200 Vac mode 1 208 Vac mode 220 Vac mode 7 3 2 7 3 4 7 3 5 006 DRWNETRT XX 136 DRWNETRT XX 136 DRWNETR...

Page 20: ...1 By pass mode 8 7 Overtemperature 8 10 Inverter undervoltage 8 13 DC BUS line overvoltage 8 4 Battery needs replacing 8 2 Overload 8 8 Battery charge failure 8 11 Inverter overvoltage 8 14 High AC i...

Page 21: ...without the need to install any additional software Once connected recognition of the UPS occurs in the same way as for any other peripheral and the operating parameters can be managed by way of the...

Page 22: ...t Tx Rx GND C SW1 SW2 GND R R1 General alarm R2 No mains R3 Battery low R4 On by pass R5 Overload R6 Overtemperature 9 5 1 1 9 5 1 3 9 5 1 2 SW1 SW2 relay contact OFF OFF NO ON OFF NC GND R Relay grou...

Page 23: ...99 seconds maximum 3 Press 3 to configure NO or NC operation of each relay Shift SW2 to the ON position to activate the settings If SW2 is returned to the OFF position SW1 can be used to check the NO...

Page 24: ...f 8 hours UPS in overload Disconnect non essential loads Depleted batteries The batteries will degrade quickly if used fequently or in high operating temperatures Should the batter ies have reached th...

Page 25: ...ut output RJ11 or RJ45 Technology On line double conversion VFI SS 111 Batteries Type Maintenance free sealed lead life expectancy 3 5 years Typical backup 7 minutes 7 minutes 7 minutes 8 minutes Comm...

Page 26: ...wowiejska St 21 25 00 665 Warszawa Tel 48 0 22 2345 223 Fax 48 0 22 2345 223 ups poland socomec com PORTUGAL Rua Moinho do Cuco Bloco A Lj Dta Paz 2640 566 MAFRA Tel 351 261 812 599 Fax 351 261 812 57...

Reviews: