43
MODULYS GP Green Power 2.0
range from 25 to 200 kVA - Ref.: IOMMODGPXX05-GB 01
ENGLISH
10-1
10. STANDARD FEATURES AND OPTIONS
ADC CARD
This card can be configured to control four outputs and three digital inputs. The first output can be configured as normally open
(NO) or normally closed (NC). The other three outputs are configured as normally open (NO).
A maximum of two cards can be installed on each unit. If more than one ADC card is used simultaneously, the configurations must
be different. The card must be inserted in slot S1 or S2.
All the configurations have to be selected only by SOCOMEC service personnel through SOCOMEC maintenance software.
• Electrical data
- Permitted Nominal current and voltage of NO or NC contacts: 4 A 250 Vac
- Inputs are activated on loop closing or opening depending on the configuration.
• External UPS power OFF connection
A remote shutdown system command (UPS power OFF) can be installed by means of the optional ADC card. Connect a zero-
potential contact to terminals IN1+ and IN1- of the ADC card. The UPS power OFF input is normally disabled. It can be enabled
only by SOCOMEC service personnel.
• Connection of the generator
If your system uses a generator connect the ‘generator set ready’ no-potential contact to connector IN 2 on the optional ADC
card configured in standard or power safe mode. This automatically extends the voltage and frequency value range when power is
supplied by the generator set.
EXTERNAL TEMPERATURE SENSOR
The ADC card has the possibility of connecting an external NTC sensor, to measure the external battery cabinet temperature.
RS485
The ADC card also has a RS485 serial port to connect an external device.
NET VISION CARD
NET VISION is a communication and management interface designed for business networks. The UPS behaves exactly like a
networked peripheral, it can be managed remotely, and allows the shutdown of network workstations.
NET VISION allows a direct interface between the UPS and LAN network avoiding dependence on the server and support SMTP,
SNMP, DMCP and many other protocols. it interacts via the web browser
Dry
contact
NTC sensor
RS485