MODULYS GP Green Power 2.0
range from 25 to 200 kVA - Ref.: IOMMODGPXX05-GB 01
2. ENVIRONMENTAL REQUIREMENTS AND HANDLING
2.1-1
Top air vent (optional)
2.1-2
Rear air vent
NOTE!
Before carrying out any operations on the unit read the Safety standards chapter carefully.
2.1. ENVIRONMENTAL
REQUIREMENTS
Install the unit in an equipment room where only skilled technicians have access. The room must be:
• of a suitable size
• free from conductive, inflammable and corrosive items;
• not exposed directly to sunlight.
The floor must support the weight of the unit and guarantee its stability. The unit is designed for indoor non-air-conditioned
rooms only.
1. Up to 7+1 modules; 60 cm if 8+0 modules.
15 cm
1,5 m
15 cm
15 cm
15 cm
130°
≥ 80 cm
130°
15 cm
15 cm
1,5 m
15 cm
40 cm
(1)
40 cm
(1)
40 cm
(1)
40 cm
(1)
1,5 m
15 cm
15 cm
15 cm
130°
≥ 80 cm
130°
15 cm
15 cm
1,5 m